camber.agent turns CAMBER's deterministic results into plain-language, cited explanations and natural-language Q&A — strictly grounded in the analytics layer, provider-agnostic, and fully useful with no LLM wired at all.

flowchart LR
  q["question / findings"] --> ctx["build_context -> Context of Facts"]
  ctx --> block["to_prompt_block (only surface to model)"]
  block --> client{"complete() client wired?"}
  client -- no --> tmpl["explain_from_facts (deterministic template)"]
  client -- yes --> llm["LLM answer (cite every [id])"]
  llm --> verify["verify.check (strict)"]
  verify -- grounded --> ans["Grounded (cited rule + standard)"]
  verify -- empty --> tmpl
  tmpl --> ans
Facts are the only surface shown to a model; strict verification repairs or falls back to the template.

Three principles, enforced in code (tests/test_agent_readonly_guard.py):

  1. Grounded — an answer may only cite facts CAMBER produced, and every number it states must be traceable to one. Ungrounded content is flagged (and, in strict mode, repaired away).
  2. Provider-agnostic — no LLM SDK is imported, no vendor is named, and nothing here touches a network. You inject a complete(prompt, **opts) -> str callable; the deterministic layer works without one.
  3. Read-only — the agent explains and answers; it never writes back to a BAS.

The grounding surface — Context of Facts

A Fact(id, kind, equip, text, data) is one citable statement built from an existing deterministic object. Its text comes straight from that object's template surface (Finding.summary, Recommendation title + action, FaultCost basis/dollars) and its data is the object's as_dict(). Ids are order-stable and deterministic (F1, C1, R1, G1, … per kind) so citations are reproducible.

from camber.agent import build_context

ctx = build_context(findings, loads=loads, price=price)
print(ctx.to_prompt_block())
# [F1] (finding, AHU-1) Both coils open 20% of hours.
# [C1] (cost, AHU-1) Estimated annual cost ≈ $2,897 (8,802 kWh, 1,314 therms; reheat-gas+paired-cooling).
# [R1] (recommendation, AHU-1) Lock out simultaneous heating and cooling. ...

to_prompt_block() is the only thing ever put in front of a model — it cannot invent equipment or metrics that aren't in the fact set. Builders exist for every deterministic layer: facts_from_findings (finding + cost + recommendation + root-cause), facts_from_run, facts_from_scorecard, facts_from_completeness (why a rule couldn't run), facts_from_history (bounded stats only, never raw series), and facts_from_mapping.

A cost fact never fabricates a dollar figure: when the estimate is uncosted it states the basis / missing input ("No dollar figure — no cost model for rule 'unmet_setpoint_hours'.") instead of a number.

Explain a finding — explain

from camber.agent import explain

g = explain(findings, loads=loads, price=price)  # no client -> deterministic template
print(g.text)  # grouped by equipment, every claim cited [F1]/[C1]/[R1]
print(g.source)  # "template"
print(g.grounded)  # True

With no client, explain returns the deterministic templates.explain_from_facts answer — fully grounded, no LLM. This is also the regression oracle the LLM path is verified against.

Ask a question — ask

from camber.agent import ask

ask("what should I do about AHU-1?", ctx).text  # -> [R1] Lock out simultaneous heating ...
ask("what will this cost?", ctx).text  # -> [C1] Estimated annual cost ≈ $2,897 ...

Without an LLM, ask routes the question over the fact set by keyword / equipment / kind and answers honestly ("I don't know — no matching fact …") when nothing applies. It accepts a prebuilt context, or builds one from findings / run / read_api / scorecard / completeness / mapping_review.

Wiring an LLM — the provider-agnostic seam

CAMBER ships no provider. You wrap your SDK in a callable and inject it — exactly as ingest.haystack takes an injected his_read transport:

from camber.agent import client_from_callable, explain

# the contract is: complete(prompt: str, **opts) -> str   (opts: system, max_tokens, temperature)
client = client_from_callable(lambda prompt, **opts: my_provider.complete(prompt))

g = explain(findings, client=client, loads=loads, price=price)
g.source  # "llm"
g.cited  # ["F1", "R1"] — ids that resolve to real facts
g.grounded  # True only if every cite resolves AND every number is traceable
g.flagged  # problems found (unknown-citation / uncited-number)

The model is prompted with the fact block and instructed to cite every claim with its [id] and to say it doesn't know when a fact isn't present.

Verification — how grounding is enforced

Every generated answer runs through verify.check(text, context, *, strict=True):

  • an answer is grounded when every [id] it cites resolves to a real fact and every number it states appears in a cited fact's text or data (number-traceability);
  • strict mode (default) repairs the text — dropping sentences that state an untraceable number and stripping unknown [id] tokens — so a partly-hallucinated answer degrades to its grounded subset instead of misleading;
  • if strict verification empties the answer, explain/ask fall back to the deterministic template — you always get a useful, grounded response.
  • require_cite_each_sentence=True (0.107, #194) is the stricter mode the RCx report's prose slots use: a sentence with no [id] that resolves is flagged uncited-sentence and dropped, and each sentence's numbers must appear in the facts that sentence cites.
  • a fact id may be context-qualified, [F1@ctx] (0.107): the part after @ (letters, digits, _, -) says where the fact lives. Plain [F1] ids work as before.

Grounded(text, cited, facts, grounded, flagged, source) — source ∈ {"llm", "template"} tells you which path produced the answer.

Guarantees

  • No vendor, no network — tests/test_agent_readonly_guard.py parses the AST of every camber/agent/*.py (and mapping_assist.py) and fails if any LLM SDK or network client is imported.
  • Read-only — the same guard fails on any write/command/actuation symbol.
  • Useful with zero LLM — the template layer is a complete, grounded implementation on its own.

Used by assisted point mapping's LLMSuggester, which proposes roles through this same seam and re-scores them deterministically.