The drift families ask "is this slowly getting worse?"; this family asks a control-sequence question: "is the plant's setpoint-reset logic doing what ASHRAE Guideline-36 intends?" G36 replaces fixed supply-air-temperature and duct-static setpoints with reset schedules — an OAT-driven SAT target, and Trim-and-Respond (T&R) loops driven by per-zone requests. When that reset logic is missing, mis-scheduled, or dominated by one rogue zone, the plant burns avoidable reheat and fan energy while every instantaneous check still reads "in range."

flowchart TD
    zones["per-zone temps"] --> req["requests (cooling_sat_requests / static_pressure_requests)"]
    req --> tr["Trim-and-Respond (tr_simulate)"]
    oat[OAT] --> map["OAT to SAT target (oat_sat_setpoint)"]
    tr --> sp["reset setpoint (SAT / duct static)"]
    map --> comp["supply_air_reset_compliance (right target?)"]
    sp --> eff["reset_effectiveness (trimming and responding?)"]
    req --> rogue["rogue_zone_census (one zone dragging?)"]
    req --> cohort["cohort_starvation (whole AHU starved?)"]

Zone requests drive Trim-and-Respond to a setpoint; the four detector questions read compliance, effectiveness, rogue zones, and cohort starvation off that pipeline.

CAMBER already ships the G36 primitives in camber.g36_reset (the OAT→SAT map oat_sat_setpoint, the T&R loop tr_step/tr_simulate with the SAT_TR/STATIC_TR parameter presets, and the per-zone request generators cooling_sat_requests/static_pressure_requests). This family wires them into rules.

The detectors

Rule Signal Sided Catches
supply_air_reset_compliance supply-air temp vs the G36 OAT-reset target up (too cold) supply air held colder than the G36 §5.16.2.2.b OAT→SAT target — an avoidable reheat/energy opportunity
sat_reset_effectiveness supply-air-temp setpoint vs the request-implied T&R trajectory two-sided a SAT reset that is stuck, not responding, not trimming, or diverging vs its own zone requests
static_reset_effectiveness duct-static setpoint vs the request-implied T&R trajectory two-sided a duct-static reset that is stuck, not responding, not trimming, or diverging vs its own zone requests
sat_rogue_zone_census per-zone SAT reset-request rate across the zone fleet one-sided (monopolizer) one chronically over-demanding zone monopolizing the SAT requests and dragging the reset colder than the fleet needs
static_rogue_zone_census per-zone duct-static reset-request rate across the zone fleet one-sided (monopolizer) one chronically over-demanding zone monopolizing the duct-static requests and dragging the reset higher than the fleet needs
static_cohort_starvation per-zone request rate, cohort-wide simultaneity per AHU cohort common-mode most/all of an AHU's zones requesting the duct-static reset at once → one upstream fault (fan/static SP/upstream damper), not N zone faults
sat_cohort_starvation per-zone request rate, cohort-wide simultaneity per AHU cohort common-mode most/all of an AHU's zones requesting the SAT reset at once → cooling/reset maxed (caveated as a possible design-day)

SAT-reset compliance vs the existing supply_air_reset. These are complementary detectors on the same signal. supply_air_reset (camber.satreset) asks the shape question — does supply air get reset upward at all as cooling load drops (a positive slope)? supply_air_reset_compliance asks the target question — is supply air held colder than the specific G36 OAT→SAT map would command? A plant can have a healthy reset slope yet still sit below the G36 target, and vice-versa, so both are worth running.

The G36 map (oat_sat_setpoint, §5.16.2.2.b) holds SAT at min_clg_sat (55 °F default) when it is hot out (OAT ≥ oat_max, 70 °F) and resets it up toward t_max (65 °F) when it is cool (OAT ≤ oat_min, 60 °F). The rule compares actual SAT to that OAT-computed target — not to a mapped SUPPLY_AIR_TEMP_SP — so it works on a typical trend export carrying only SAT and OAT. It is one-sided (only SAT colder than the target is an opportunity; running warmer than min_clg_sat is the energy-saving direction) and warn-level (an opportunity, not a hard fault), warning when SAT runs below target warn_pct % of the hours and the mean gap clears warn_gap_f (so a trivially small persistent gap does not flag). The four G36 map parameters are constructor arguments, so a site can match its own reset schedule (make_rule("supply_air_reset_compliance", oat_min=…, min_clg_sat=…)). Thresholds are screening / opportunity-grade (provisional-untuned). OAT is building-level and arrives via the runner's shared channel; the rule declines loudly when it is unmapped.

Reset effectiveness — is the reset actually trimming-and-responding?

supply_air_reset_compliance above asks whether SAT sits at the right target; reset effectiveness asks whether the reset mechanism works at all. Given the plant's own aggregated per-cycle reset-request count (SAT_RESET_REQUESTS / STATIC_PRESSURE_REQUESTS) alongside the actual reset setpoint (SUPPLY_AIR_TEMP_SP / DUCT_STATIC_SP), the rule reconstructs the setpoint that Trim-and-Respond should have produced (tr_simulate, G36 §5.1.14) and compares it to the trended setpoint. It flags four modes:

  • stuck — the setpoint barely moves while the request pattern would have moved it (a frozen or overridden reset);
  • not responding — under sustained demand the setpoint sits at the energy-saving (trim) end instead of responding toward demand (zones starve);
  • not trimming — while zones are idle the setpoint stays parked at the demand end (energy wasted);
  • diverges — the setpoint moves the opposite way to the T&R command on most cycles (an inverted or mis-wired reset).

It ships as two instances — sat_reset_effectiveness (supply-air-temp setpoint, °F, SAT_TR preset) and static_reset_effectiveness (duct-static setpoint, in. w.c., STATIC_TR preset) — sharing one reset-agnostic camber.g36_reset.reset_effectiveness analyzer. It is two-sided (both starving and wasting are faults) and warn-level (an operational opportunity, not a hard equipment fault). Unlike the compliance rule it needs the reset setpoint and the request count both mapped, so it declines loudly on the common trend export that carries no request point. The reconstructed-trajectory error (mean_abs_error_sp) is informational only — a coarser trend cadence than the controller inflates it, so the verdict rests on the cadence-robust mode detectors above, not the raw error. Thresholds are screening / opportunity-grade (provisional-untuned).

Rogue-zone census — which zone is dragging the reset?

The two rules above look at the reset setpoint; this one looks at the demand side that drives it. In G36 the SAT / duct-static reset responds to the high-percentile of per-zone requests (§5.14.8), so one chronically over-demanding zone can monopolize the requests and drag the whole reset — forcing a colder supply-air temperature or higher duct static than the rest of the fleet needs. The plant then serves one bad box at everyone else's energy expense.

sat_rogue_zone_census and static_rogue_zone_census are fleet rules (many zones in, one aggregate Finding out). Across the zone fleet each computes every zone's per-cycle request series — a vectorized form of cooling_sat_requests / static_pressure_requests — then scores each zone by its share of the group's total requests and the fraction of active cycles on which it holds the binding (maximum) request. A zone is flagged as a rogue when it both holds the binding request a dominant fraction of the time and commands a disproportionate share of the requests. Requiring both is what keeps a uniformly-busy fleet quiet: when every zone is equally hot they all tie at the binding max, but their shares are equal, so none is singled out.

Topology honesty (auto-scoping). Deciding that a zone drags AHU-1's reset requires knowing which zones AHU-1 serves. The census now scopes per air handler automatically whenever a served-by topology is available, and the caveat it attaches reflects how trustworthy that grouping is:

  • Semantic topology (from a Brick feeds / Haystack ahuRef model, passed as run_fleet(..., topology=site.topology)) — the census scopes per air handler (a rogue is compared only to its siblings, in rogue_by_group) and the confound caveat drops.
  • Naming-heuristic topology — when no semantic model is supplied, Registry.run_fleet auto-builds a grouping from the equipment ids themselves (AHU_1_VAV_3 under AHU_1), so the census scopes per-AHU even with no model — but keeps a softened screening caveat because the grouping is inferred, not verified.
  • Partial coverage — zones the topology does not cover are pooled together (building-wide fallback) and that remainder is caveated; the covered zones are still scoped.
  • No topology — the original building-wide pool with the full confound caveat (a zone flagged in the single pool may simply serve a hotter air handler, so it is a screening signal only).

The grouping and its provenance are recorded in the finding's metrics (grouped, grouping_provenance, n_zones_ungrouped). The census also declines loudly — demoting a clean "ok" to info — when zones were unevaluable or no zone generated any request (the reset is not demand-bound, so nothing can be dragging it). Thresholds are screening / opportunity-grade (provisional-untuned).

Cohort starvation — the common-mode twin

The rogue-zone census finds an outlier — one zone dominating the requests. Its mirror image is a common-mode pattern: when most or all of an air handler's zones raise reset requests at the same time, that is not many independent zone faults, it is one upstream fault the reset cannot fix — a duct-static setpoint capped too low, a supply fan maxed out or failing, or a restricted upstream damper (SAT side: cooling capacity or the reset maxed). static_cohort_starvation and sat_cohort_starvation group each AHU's zones (per the same topology machinery) and flag a group when a high fraction of its zones request simultaneously on a sustained fraction of the active cycles. The finding names the air handler and says look upstream, not at individual zones.

The two twins are provably distinct shapes on the same signal: a lone rogue never reaches the cohort-wide fraction, and a starved cohort shares its requests too evenly to concentrate in one zone — so a rogue never trips starvation and a starved cohort never trips the rogue census. Both scope per air handler with the same provenance/coverage-aware caveat (semantic drops it, heuristic softens it, partial pools the remainder). The SAT variant carries an extra caveat: a whole cohort running warm can be a genuinely hot design-day rather than a capacity fault, so corroborate with OAT before acting.

Dollar impact

camber.fault_economics prices the reset family's findings so an operator can rank the backlog by money, not just severity (triage-grade, not audit-grade):

  • supply_air_reset_compliance → avoidable terminal reheat: reheat-coil capacity × below-target hours × diversity, scaled by the below-target gap (mean_gap_f) so a bigger gap costs more. Needs the reheat-coil sizing (EquipmentLoad.heating_capacity_kbtuh), else uncosted.
  • static_reset_effectiveness (not_trimming) → wasted fan energy (static SP parked high while zones are idle): fan_kw × idle-untrimmed fraction × excess. sat_reset_effectiveness (not_trimming) → avoidable reheat (SAT parked cold).
  • The other reset-effectiveness modes are uncosted by design — not_responding (zones starve) is a comfort/capacity risk, and stuck / diverges have an indeterminate energy sign; the estimator returns an honest basis rather than fabricating a dollar figure.

  • sat/static_rogue_zone_census → the whole air handler over-services (colder SAT / higher static) because one zone drags the reset: reheat / fan waste scaled by the rogue's request share (worst_zone_share). Uncosted when the census is ungrouped (a building-wide screening signal, not a per-AHU verdict).

  • static_cohort_starvation → sustained fan over-pressure from the upstream fault, scaled by the cohort's sustained fraction; sat_cohort_starvation is unmet-load/comfort → uncosted.

Because these findings are fleet-level (equip="<fleet>"), the estimator attributes sizing to the offending air handler named in the metrics (worst_group, or the group holding worst_zone), so a {equip: EquipmentLoad} map keyed by AHU costs each starved/dragged handler on its own fan/coil.

Family complete

The Trim-and-Respond / G36-reset family now spans seven detectors on the shared camber.g36_reset engine (oat_sat_setpoint, tr_step / tr_simulate, cooling_sat_requests / static_pressure_requests): SAT-reset compliance (does the reset sit at the right target?), reset effectiveness for SAT and static (does the reset actually trim and respond?), the rogue-zone census for SAT and static (is one zone dragging the reset?), and its common-mode twin cohort starvation for SAT and static (is a whole AHU cohort starved by an upstream fault?). The census family scopes per air handler automatically via the served-by topology — semantic (from a Brick/Haystack model) or a naming heuristic run_fleet auto-builds.