Chiller drift detection & threshold calibration
Most FDD asks "is this reading bad right now?" Drift detection asks a harder, quieter question: "is this machine slowly getting worse than it used to be?" A chiller can pass every instantaneous check while its condenser fouls, its charge leaks, or its evaporator feed degrades over months. CAMBER catches that by comparing the machine to its own frozen past, at matched load.
flowchart TD
base["load-normalized baseline (fit_load_baseline, metric ~ f(tons))"] --> stat["period statistic (load_drift_stats)"]
base --> cusum["streaming CUSUM (ApproachDriftMonitor)"]
stat --> find[per-detector Findings]
cusum --> find
find --> cond["diagnose_condenser_drift (condenser loop)"]
find --> evap["diagnose_evaporator_drift (evaporator loop)"]
cond --> whole["diagnose_chiller_drift (whole-machine locus)"]
evap --> whole
whole --> report["site report / export"]
Frozen-baseline fit feeds a period statistic and a streaming CUSUM; per-side roll-ups combine into one whole-machine verdict.

Synthetic data: driftsim with condenser fouling, drawn by drift_evidence for chiller_approach_drift. The band is the frozen baseline's fit ± 2 residual sigmas; at matched load the current approach sits 2–3 °F above it.
All of these detectors are period rules — run them with
Registry.run_periods against a baseline period and a current period. Each
freezes a load-normalized baseline into a BaselineStore on first use, so the reference
survives between runs instead of drifting along with the fault.
The load-normalized baseline
A chiller's approach, subcooling and superheat all move with load, so a raw month-to-month comparison
confuses "ran harder this month" with "degraded this month." Every detector fits
metric ~ f(tons) over the baseline period (camber.chillerbaseline.fit_load_baseline) and scores
the current period as the residual against that fit — the drift at matched load. Two readouts come
off the same frozen baseline:
- a period statistic — how far the current period sits above/below the baseline, in °F and in
baseline sigmas (
camber.chillerbaseline.load_drift_stats); - a sustained-shift alarm — a streaming tabular CUSUM
(
camber.chillerdrift.ApproachDriftMonitor) that fires only when the signal moves and stays moved, not on a single hot hour.
Machines of any size. The load gates were absolute (a 5-ton floor and a 10-ton span to identify
a slope) — 10 % and 20 % of a 50-ton machine — so a 5-ton chiller or a 3-ton heat pump declined
every time. Since 0.82.0 every tons-normalized chiller rule takes min_tons / min_tons_span, and
by default derives them from the baseline's observed capacity
(camber.chillerbaseline.size_relative_load_gates: 10 % / 20 % of the 95th-percentile load, capped
at 5 t / 10 t, so any machine of 50 t or more gets exactly the gates it always had). A machine whose
load does not move enough to identify a slope (fixed capacity, single stage) gets a flat level
baseline instead of a decline; it is only scored at the load it was observed at, and the finding
says so.
Plausibility bands are physical, per metric. The fit's default band (0–50 °F) suits approach,
not superheat or subcooling: liquid floodback reads ~0 °F superheat and, with transducer error, a
few °F below zero; flash gas does the same to subcooling; a starved evaporator runs superheat past
50 °F. Filtering those out discarded the fault itself (floodback declined; a half-flooded period
scored "ok −0.1 °F"). Superheat now uses −20…150 °F and subcooling −20…80 °F, shared with
camber.sensorhealth.PHYSICAL_BOUNDS, which still reject sentinel codes. Refrigerant pressures use
−15…2000 psig (discharge) and −15…1000 psig (suction) — genuinely refrigerant-neutral, covering a
CO₂ (R744) transcritical gas cooler at 1100–1750 psig, which the former 700 / 400 psig ceilings
rejected wholesale.
A second regressor where physics demands one. Head pressure is set first by the heat-sink
temperature and suction pressure by the leaving chilled-water temperature — load comes second. So
fit_load_baseline(..., covariate_col=...) fits metric ~ load + covariate and every score is made
at matched load and matched condition (LoadBaseline.predict(tons, covariate); the CUSUM folds
the reading referred to the baseline's reference condition, LoadBaseline.adjust). A covariate is
used only when its 5–95 % spread in the baseline is at least 2 °F (four times a plant sensor's
accuracy) and its fitted effect has the physically expected sign; otherwise the rule falls back to
load only and says why.
The CUSUM accounts for serial correlation. Its slack and limit are in sigmas of independent
samples, but trend residuals wander slowly — lag-1 autocorrelation 0.8–0.9 at 1–5 minute cadence on
real plant data — so one half-hour excursion sampled every minute was counted thirty times. On the
normal days of a real 5-ton chiller that made the sustained alarm fire on 50–90 % of days
(subcooling, 5-min / 1-min data). The fitted baseline now records its residual lag-1
autocorrelation (LoadBaseline.resid_lag1, zero unless significant) and the monitor expresses its
parameters in the residual's long-run sigma, σ·√((1+ρ)/(1−ρ)), carrying ρ to the current
period's cadence as ρ^(Δt/Δt_baseline). Hourly trend data with independent residuals is
unchanged. A CUSUM also has no °F floor, so it will (correctly) flag a sustained shift smaller than
the period rule's magnitude floor — e.g. a machine run at loads outside its baseline envelope for a
season. That is a tuning question for the provisional parameters below, not a defect, and they are
left as they are.
The detector family
| Detector | Signal | Sides | Catches |
|---|---|---|---|
ChillerApproachFouling / ChillerApproachDrift |
condenser/evaporator approach | one-sided (up) | heat-transfer loss (fouling, air/water flow) |
ChillerSubcoolingDrift |
liquid-line subcooling | two-sided | refrigerant charge (under/overcharge, non-condensables) |
ChillerSuperheatDrift |
suction superheat | two-sided | evaporator feed (overfeed/floodback vs. starvation) |
ChillerCwRangeDrift |
condenser-water range / ΔT | two-sided | condenser-side hydraulics |
CoolingTowerApproachDrift |
tower approach (CW supply − wet-bulb) | one-sided (up) | tower heat rejection (fouled/scaled fill, plugged nozzles, reduced airflow) |
CoolingTowerFanEffortDrift (0.92) |
tower fan speed at matched load and wet-bulb | one-sided (up) | the same faults on a tower whose fan controller holds the approach -- it works harder instead (see Plant detectors) |
ChillerHeadPressureDrift |
discharge / condensing pressure | one-sided (up) | high-side heat rejection (fouling/scale, non-condensables, reduced CW flow), read off the gauge |
ChillerSuctionPressureDrift |
suction / evaporating pressure | two-sided | low-side evaporator condition — a fall is heat-transfer loss / low charge / starved feed, a rise is overfeed / flooding |
The condenser side pairs up. ChillerCwRangeDrift (hydraulics) and CoolingTowerApproachDrift
(tower heat rejection) sit on the same condenser water loop as the chiller's condenser approach — a
widening tower approach raises condenser-water temperature, chiller lift, and kW/ton, so it shows up
downstream in the chiller too. The tower approach is one-sided (fouling only widens it) and is scored
against a load-normalized baseline just like the chiller detectors; wet-bulb is taken measured, or
derived from outdoor dry-bulb + RH (Stull) when it isn't a BAS point. Stull's fit assumes sea-level
pressure; pass elevation_ft (or a measured pressure_psia) to the tower rules and wet-bulb is
solved psychrometrically at site pressure instead (at 1600 m in hot, dry air the sea-level value
reads ~2.6 °F high, understating the approach). Since 0.98 a config's top-level
site_elevation_ft sets it once for the tower drift detectors, cooling_tower_approach and
condenser_water_reset (see CLI.md).
One condenser-loop verdict. These four condenser-side signals fail independently (a scaling
tube, a throttled valve, a fouled tower, and a rising high-side pressure localize different things) but
corroborate when a problem is system-wide. camber.condenserdrift.diagnose_condenser_drift(findings)
reads the individual drift Findings and returns one localized CondenserDriftDiagnosis — naming the
cause of each drifting signal (tube fouling/scale · reduced CW flow vs. bypass · tower heat-rejection ·
high-side pressure rising) and flagging corroboration when two or more agree. It isolates the
chiller condenser leg from the evaporator leg (the approach rule scores both), and for head pressure it
removes the entering-CW-temperature confound at source when head pressure is regressed on it (a
fouled tower then reads as a tower fault with a healthy chiller high side, not a corroborated pair);
when head pressure had to fall back to load only, it uses the tower signal to disambiguate — a
co-moving CW-temp rise backed by a degrading tower corroborates a real heat-rejection fault, while
the same rise with a quiet tower is flagged as likely ambient rather than a high-side fault. Stays screening-grade:
corroboration raises priority and specificity, not the severity tier — the thing that turns a set of
screening alerts into a work order.
Surfacing the verdict. The per-loop verdicts flow downstream like the chiller, pump, and AHU
ones: camber.integrate.export.condenser_diagnoses_to_frame / export_condenser_diagnoses write one
row per loop (severity · corroborated · joined causes · caveat count · fingerprint — note there is
no locus / loop-wide column, since the condenser diagnosis carries neither) to CSV/JSON/Parquet,
and camber.report.condenser_diagnosis_table renders a worst-first HTML table.
build_site_report(..., condenser_diagnoses=[...]) splices that table into the owner-facing site
report, alongside the chiller, pump, and AHU verdict tables.
Head pressure is the high side, read directly. ChillerHeadPressureDrift trends the discharge /
condensing pressure (Role.DISCHARGE_PRESSURE, psig) — the same fault modes that widen the condenser
approach (fouling/scale, non-condensables, reduced CW flow) also raise head pressure, but the pressure
is directly instrumented, often earlier, and it is what a mechanic actually gauges. It is one-sided
like approach (only a rise is a fault). Its confound is regressed out, not just flagged: head
pressure climbs with the heat-sink temperature at least as much as with load, so the baseline is
pressure ~ load + entering condenser-water temperature (Role.CW_SUPPLY_TEMP, water-cooled) or
+ outdoor-air temperature (Role.OAT, air-cooled) when either is mapped and varied in the
baseline. On a residential heat pump's lab data that cut the baseline scatter from ~61 psi (load
only) to ~5 psi, and head-pressure recall on the labeled faults from 1 % to 32 % with no false
alarms. Without a usable heat-sink temperature the rule falls back to load only, says so in a
caveat, and reports and caveats a co-moving CW-supply rise as before; a mapped
Role.SUCTION_PRESSURE adds the condensing-over-suction lift as further context. Absolute head pressure is refrigerant-dependent, so
the sigma floor carries the weight (self-scaling against the baseline's own scatter) and the psi
floor is only a coarse backstop.
Suction pressure is the low side, read directly. ChillerSuctionPressureDrift is the evaporator
twin: it trends the suction / evaporating pressure (Role.SUCTION_PRESSURE, psig). At matched load a
fall is the evaporator heat-transfer-loss / low-charge / starved-feed signature and a rise is
overfeed / flooding, so unlike head pressure it is two-sided (both directions are faults, scored on
magnitude with the sign reported), sharing head pressure's psi/σ floors because it is the same raw-gauge
signal class. Its confound is the mirror of head pressure's: suction pressure tracks chilled-water
supply temperature, so a chilled-water reset lifts it with no fault. When CHW supply varied in the
baseline the fit is pressure ~ load + CHW supply and the reset is accounted for (on a real 5-ton
chiller a reset to 52.7 °F read as a +9σ suction fault under load-only normalization and −0.6σ
with it; false alarms on normal days fell from 33 % to 0 %). With a fixed setpoint in the baseline
the rule falls back to load only and caveats a co-moving CHW-supply move as possibly
setpoint-driven.
Subcooling and superheat are complementary. Subcooling watches the condenser/liquid side (how much liquid is standing in the condenser); superheat watches the evaporator/suction side (whether the evaporator is fed correctly). Both are two-sided because both directions are genuine faults — subcooling falls on undercharge and rises on overcharge; superheat falls on overfeed (liquid-floodback risk) and rises on starvation. The magnitude is scored symmetrically and the direction is reported alongside, so an equal rise and fall score identically while the sign says which fault it is.
One evaporator-loop verdict. Mirroring the condenser side, three evaporator-side signals — the
chiller's evaporator-approach leg (heat transfer), superheat (feed), and suction pressure
(the low-side pressure itself) — combine in camber.evaporatordrift.diagnose_evaporator_drift(findings),
which returns one localized EvaporatorDriftDiagnosis naming each cause (tube fouling/scale ·
overfeed-floodback vs. starvation · heat-transfer loss/low-charge vs. overfeed/flooding) and flagging
corroboration when two or more agree. It isolates the evaporator leg from the condenser leg (the
approach rule scores both). Because superheat and suction pressure are two reads on the same
feed/charge axis, it cross-checks them: both agreeing on overfeed (falling superheat + rising
suction) or on starvation (rising superheat + falling suction) is a strong, specific verdict, while a
disagreement is called ambiguous rather than asserted — the low-side twin of the tower-disambiguates-
head-pressure check on the condenser side. Screening-grade and pure over Findings.
Surfacing the verdict. Like the condenser side, the per-loop evaporator verdicts flow downstream:
camber.integrate.export.evaporator_diagnoses_to_frame / export_evaporator_diagnoses write one row
per loop (severity · corroborated · joined causes · caveat count · fingerprint — no locus /
loop-wide column, as the diagnosis carries neither) to CSV/JSON/Parquet, and
camber.report.evaporator_diagnosis_table renders a worst-first HTML table.
build_site_report(..., evaporator_diagnoses=[...]) splices it into the owner-facing site report,
alongside the chiller, condenser, pump, and AHU verdict tables.
One whole-machine verdict. camber.chillerdiag.diagnose_chiller_drift(findings) rolls both side
diagnoses into a single per-chiller ChillerDriftDiagnosis and adds the cross-side reasoning neither
side can do alone: only the condenser side degrading localizes to the condenser loop, only the
evaporator side to the evaporator, but both sides drifting together points at a circuit-wide
cause (refrigerant charge, non-condensables, a compressor / metering fault) rather than one fouled
heat exchanger. Liquid-line subcooling folds in as the dedicated charge signal — a subcooling drift
alongside both sides moving corroborates a charge / inventory problem. It reports a locus (steady ·
condenser · evaporator · charge · whole-machine) and a machine_wide flag, so a screening pass can
separate "one exchanger needs a walkdown" from "gauge the whole machine". Screening-grade; re-uses the
side diagnoses unchanged.
Instrumentation gating
Subcooling and superheat are differences against a saturation temperature, and discharge/suction
pressure are raw pressures. A chiller that publishes the differences maps them directly
(Role.SUBCOOLING_TEMP, Role.SUPERHEAT_TEMP). Since 0.93 one that trends only pressures and line
temperatures gets them derived: name its refrigerant on the config's equipment entry ("refrigerant":
"R-410A"), map the line temperatures (liquid_line_temp, suction_line_temp), and CAMBER computes
subcooling, superheat and both approaches from its saturation curve (see
Refrigerant properties). Many chillers publish neither, so the rule that depends on a
point declines with a caveat when it is absent. A chiller missing from a charge, feed or high-side
report must never read as a healthy one.
Thresholds are honest about what they are
Every finding is labelled with two threshold classes (camber.driftthresholds), because they are not
provisional in the same way:
- Magnitude floors (
warn_f,fault_sigma, …) are screening-grade: characterized for the signal class and good enough to rank a walkdown, but not established on your specific machines. - Temporal / CUSUM parameters are provisional-untuned: textbook starting points whose false-alarm rate and detection delay have never been measured on real chiller trends.
Read a sustained alarm as "worth looking at now," never as a dispatch-grade verdict — until you calibrate.
Running the family
From a config, no Python needed — add a drift section naming this family ("family": "chiller") and run
camber drift freeze once to establish the references, then camber drift run to score. camber
run folds the verdicts into the ordinary audit report. Only freeze (and the attributed
accept_new_normal) ever writes a baseline; scoring is read-only. See
CLI.md.
camber drift freeze config.json # establish the references (refuses to overwrite)
camber drift run config.json # score current vs baseline, worst-first
camber drift accept config.json --equip <EQ> --by <NAME> --reason "<what changed>"
Calibrating the thresholds
Every threshold above is a constructor argument, so tuning is a config change, not a code change.
When you have chiller periods with confirmed, dated fault events, camber.driftvalidation turns
that evidence into a calibrated operating point.
No labelled data yet? Characterize on physics. camber.driftsim generates physically consistent
(baseline, current) frame pairs for a healthy chiller and for the standard fault families (condenser
fouling, reduced CW/evaporator flow, tower degradation, under/overcharge, non-condensables, excess
oil), imposing each fault's known signature at a graded severity. It runs the whole suite + roll-up
end-to-end (diagnose_frames) and scores localization (locus_confusion) — on clear faults the
roll-up lands on the right locus at ~100% with no false alarms on healthy periods, and its
SimulatedCase.to_labeled(relevant=…) feeds the same evaluate/sweep per-detector ROC below. This
turns screening-grade thresholds into characterized ones; real-data tuning still refines them.
flowchart LR
sim["physics sims (driftsim / condensersim / evaporatorsim)"] --> cases["make_cases ((baseline, current) pairs)"]
cases --> diag["diagnose_frames (suite + roll-up)"]
diag --> loc["locus_confusion / cause_confusion (localization)"]
cases --> lbl["SimulatedCase.to_labeled"]
lbl --> roc["driftvalidation evaluate / sweep (per-detector ROC)"]
roc --> cal[calibrated thresholds]
Without labelled data, physics sims characterize localization and per-detector ROC; real fault periods then calibrate.
from camber.driftsim import make_cases, locus_confusion
lc = locus_confusion(make_cases(), min_severity=3) # localization on the clear faults
print(lc.accuracy, lc.as_dict()["matrix"])
The condenser heat-rejection family has its own physics validator. Because
diagnose_condenser_drift produces a cause + corroboration verdict (not a locus),
camber.condensersim characterizes it with a CauseConfusion instead: it models the coupled loop —
condensing temperature TCOND = CWS + condenser approach, entering water CWS = wet-bulb + tower
approach — so co-movement is emergent (tube scaling widens the condenser approach and lifts head
pressure; a fouling tower lifts CWS and head pressure), and it includes the negative confound
ambient_cw_rise — a CW/head rise with a quiet tower that the head-pressure confound must demote
to likely-ambient rather than flag. On clear faults it names the right cause and sets the right
corroboration flag at ~100% with no false alarms, and SimulatedCase.to_labeled(relevant=…) feeds
the same per-detector ROC.
from camber.condensersim import make_cases, cause_confusion
cc = cause_confusion(
make_cases(), min_severity=3
) # cause detection + corroboration on clear faults
print(cc.accuracy, cc.corroboration_accuracy, cc.as_dict()["matrix"])
The evaporator side has the same physics validator. camber.evaporatorsim characterizes
diagnose_evaporator_drift (also cause + corroboration, no locus) with a CauseConfusion too. It
models the low side through one shared feed latent: an overfeed lowers superheat and raises
suction pressure together, a starvation raises superheat and lowers suction — so the two feed
reads co-move and the diagnosis's superheat-vs-suction cross-check fires for real. Evaporator fouling
widens the approach alone. It includes the negative confound chw_reset — a chilled-water-supply
shift that lifts suction through the evaporating-temperature chain while superheat stays quiet, which
the cross-check correctly does not corroborate. On clear faults it names the right cause and sets
the right corroboration flag at ~100% with no false alarms.
from camber.evaporatorsim import make_cases, cause_confusion
cc = cause_confusion(make_cases(), min_severity=3)
print(cc.accuracy, cc.corroboration_accuracy, cc.as_dict()["matrix"])
from camber.driftvalidation import LabeledCase, evaluate, sweep
from camber.rules.chiller_superheat_rule import ChillerSuperheatDrift
from camber.store.modelstore import BaselineStore
# Label each (baseline, current) period pair faulty or healthy.
cases = [
LabeledCase("CH_1", baseline_df, current_df, fault=True),
LabeledCase("CH_2", baseline_df2, current_df2, fault=False),
# ...
]
# A fresh detector per case (so no case leaks its frozen baseline into another).
def build(**params):
return ChillerSuperheatDrift(BaselineStore(), site="plant", run_id="cal", **params)
# Score the shipped defaults:
score = evaluate(lambda: build(), cases)
print(score.as_dict()) # precision / recall / f1 + confusion counts
# Search a grid for the best operating point:
best = sweep(
build,
cases,
{"fault_f": [3.0, 4.0, 5.0], "fault_sigma": [6.0, 8.0]},
objective="f1", # or "recall" / "precision" / "accuracy" / "youden"
)
print(best.best_params) # feed these straight back into the rule's constructor
sweep scores every combination in the grid and returns the parameters that maximize the objective,
breaking ties toward fewer false positives (the quieter operating point wins). The harness is built
on CAMBER's FDD confusion matrix (camber.eval.confusion), so its precision/recall are the same
metrics the rest of the validation suite uses.
The shipped defaults stay screening-grade until you replace them with calibrated values — the harness is the tool for doing that against real data, not a change to the defaults themselves.