Outbound integrations
Get findings out — to ticketing, chat, email, and BI/warehouse — without coupling to any one vendor. Everything here operates on the findings layer and is read-only toward the BAS: it pushes results to people and systems, never to a controller.
flowchart LR
findings["Findings"]
ticket["finding_to_ticket"]
dispatch["dispatch_findings (severity filter, dedupe)"]
fmt["format_for"]
webhook["webhook / CMMS"]
slack["slack"]
teams["teams"]
export["export_findings"]
frame["findings_to_frame"]
files["csv / json / parquet"]
findings --> ticket
ticket --> dispatch
dispatch --> fmt
fmt --> webhook
fmt --> slack
fmt --> teams
findings --> export
export --> frame
frame --> files
Findings render to tickets, then dispatch to chat/CMMS channels or export to a tabular warehouse frame.
camber.integrate provides three layers:
- Ticket render (
tickets.py) —finding_to_ticket/findings_to_ticketsmap a Finding to a neutral, JSON-serializable CMMS work-order dict (severity→priority, stablefingerprintfor dedupe).webhook_transport(url)andcollect_transport()(in-memory, for tests/dry-runs). - Channels + dispatch (
notify.py). - Tabular export (
export.py).
Dispatch findings to a channel
dispatch_findings(findings, transport, *, channel, min_severity, site, seen, dedupe, dry_run)
renders, filters by severity, dedupes, formats per channel, and sends.
from camber.integrate import dispatch_findings, webhook_transport, email_transport
# Slack incoming webhook, only warn+ , deduped across runs
seen = load_seen() # a set of fingerprints you persist
dispatch_findings(
findings,
webhook_transport(SLACK_URL),
channel="slack",
min_severity="warn",
site="HQ",
seen=seen,
)
save_seen(seen)
# Email via SMTP (raw ticket -> subject/body)
dispatch_findings(
findings,
email_transport(
"smtp.example.com",
sender="camber@x.com",
recipients=["ops@x.com"],
username="u",
password="p",
),
channel="webhook",
min_severity="fault",
)
# CMMS / generic webhook: channel="webhook" posts the raw ticket dict
dispatch_findings(findings, webhook_transport(CMMS_URL), channel="webhook")
Channels — format_for(channel, ticket)
webhook— the raw ticket dict (for a generic JSON webhook / CMMS adapter / email).slack—slack_payload:{"text": …}with a priority emoji.teams—teams_payload: a Teams MessageCard with color + facts.
Option flags — dispatch_findings
| flag | default | effect |
|---|---|---|
channel |
"webhook" |
payload shape (webhook / slack / teams) |
min_severity |
"warn" |
drop findings below this (ok/info/warn/fault) |
seen |
None |
a fingerprint set you persist; with dedupe, only new findings send |
dedupe |
True |
skip findings whose fingerprint is already in seen |
dry_run |
False |
format but don't call the transport (returns what would send) |
site |
"" |
stamped into the ticket / fingerprint |
email_transport(host, *, port, sender, recipients, use_tls, username, password, _smtp_factory)
is a transport (subject = ticket title, body = ticket body); _smtp_factory is injectable for
tests.
Export for BI / warehouse
from camber.integrate import export_findings, findings_to_frame
df = findings_to_frame(findings, site="HQ") # one row per finding, metrics flattened
export_findings(findings, "findings.parquet", site="HQ") # csv / json / parquet by extension
Option flags — export_findings / findings_to_frame
| flag | default | effect |
|---|---|---|
format |
by extension | csv / json (records) / parquet |
flatten_metrics |
True |
metrics → metric_<key> scalar columns |
columns |
all | restrict/order the output columns |
site |
"" |