Pump / hydronic drift detection

The chiller drift family (CHILLER-DRIFT.md) asks "is this machine slowly getting worse than it used to be, at matched load?" The pump / hydronic family asks the same question of the distribution side — pumps and the loops they serve — reusing the exact same load-normalized frozen-baseline engine (camber.chillerbaseline, camber.chillerdrift), only with a duty normalizer (pump speed or flow) in place of thermal tons.

flowchart TD
    base["load-normalized baseline (camber.chillerbaseline, duty = speed/flow)"] --> det
    subgraph det["per-detector drift + CUSUM (camber.chillerdrift)"]
        d1[PumpFlowDrift]
        d2[PumpHeadDrift]
        d3[LoopDeltaTDrift]
        d4[LoopDPDrift]
        d5[PumpPowerDrift]
    end
    det --> loop["diagnose_pump_drift (per-loop locus, flow-vs-head)"]
    loop --> plant["diagnose_pump_plant (per-plant verdict)"]
    plant --> report["site report / export"]
    sim["camber.pumpsim (affinity laws)"] -. validates .-> loop

Duty-normalized baselines feed five per-detector drifts; co-movement rolls up per-loop, then per-plant, with pumpsim as the physics check.

Pump head against pump speed: the frozen baseline band and the current period falling below it as speed rises

Synthetic data: pumpsim with impeller wear, drawn by drift_evidence for pump_head_drift. At high speed the pump no longer makes the head it did.

Like the chiller detectors, each is a period rule (Registry.run_periods), freezes a load-normalized baseline into a BaselineStore on first use, reports a period statistic and a sustained-shift CUSUM alarm, labels its thresholds screening-grade / provisional-untuned (camber.driftthresholds), and declines loudly (never reads healthy) when an instrumented point is missing. They are loop-parameterized — one class serves a chilled-water or hot-water loop; the equip identifies which pump.

The detector family

Detector Signal Normalizer Sided Catches
PumpFlowDrift flow pump speed (Q ∝ N) down pump wear (impeller/wear-ring), clogged strainer, cavitation, entrained air — a flow deficit at matched speed
PumpHeadDrift differential head pump speed (H ∝ N²) down pump wear directly — a head deficit at matched speed; with flow, disambiguates pump-wear from system-resistance
LoopDeltaTDrift loop ΔT (return − supply) flow (or speed proxy) both low-ΔT syndrome (collapse: overpumping, fouled coils, stuck valves, bypass) vs underflow/starvation (widen)
LoopDPDrift loop differential pressure flow (system curve DP ∝ Q²) both rising system resistance / valve-authority loss vs bypass / stuck-open — with the DP-reset schedule subtracted out
PumpPowerDrift electrical power flow (P ∝ Q³) up wire-to-water efficiency loss (bearing/seal drag, degrading motor/drive, recirculation) — a power excess at matched flow

Loop DP is unit-free. Sites trend DP in psi, inH₂O, kPa or ftH₂O. LoopDPDrift's plausibility band is scaled to the baseline's own median DP (dp_plausible_range: −0.25…5× the median, which still rejects sentinel codes) instead of the former fixed 0–100 that assumed psi — a boiler loop with a 480.5 inH₂O setpoint was rejected sample-by-sample and the rule declined, blaming "too few loaded samples". Pass dp_range= to fix the band explicitly. Every pump/loop drift rule now names the real reason when it declines (camber.chillerbaseline.unscoreable_reason): a metric that is all missing, a load gate no sample meets (with the observed median), a band no reading falls in (check units), too few samples, or too narrow a load range.

An ok loop ΔT names no fault. Since 0.105 (#153) an ok loop_deltat_drift Finding says the ΔT "holds near its baseline" and gives the signed shift and its σ. Only warn and fault name a direction and a cause ("collapsed … low-ΔT syndrome", "widened … starvation").

Flow-at-matched-speed is the pump-wear signal. A healthy VFD pump delivers a repeatable flow at a given speed; a deficit means the pump (or its suction) has degraded. It is one-sided down — only a deficit is a fault — so ApproachDriftMonitor gained a direction="down" mode for it (alongside the existing up and both).

The confound is stated, not hidden. A flow deficit at matched speed is ambiguous between pump wear and a rise in system resistance (a throttled or stuck-closed valve downstream). Load normalization doesn't remove it, so when a loop differential-pressure point is mapped the rule reports the concurrent DP shift and caveats a deficit that co-moves with rising DP — the resistance signature, not pump wear. (The head-drift detector and the loop diagnosis, coming next in the family, resolve it further: flow↓ and head↓ → the pump; flow↓ with head steady → the distribution.)

One per-loop verdict

The four detectors fail independently (a worn impeller, a throttled valve, a fouled coil, and a lost DP setpoint are different faults) but corroborate when a problem is loop-wide. camber.pumpdrift.diagnose_pump_drift(findings) reads them and returns one localized PumpDriftDiagnosis — naming each cause, flagging corroboration when two or more agree, and running the flow-vs-head disambiguation that no single signal can do:

  • flow deficit and head deficit at matched speed → the pump itself (impeller / wear-ring / cavitation), corroborated;
  • flow deficit with head steady → the distribution (a throttled / stuck-closed valve downstream), not pump wear — look at the loop, not the impeller;
  • flow deficit with no head point → called ambiguous rather than asserted.

It splits the loop into a mechanical (pump) and a hydraulic (distribution) side and reports a locus (steady · pump · distribution · loop-wide) with a loop_wide flag — the pump-side analog of condenserdrift's tower-disambiguates-head-pressure check. Screening-grade; pure over Findings.

One per-plant verdict

Real plants run several pumps. camber.pumpplantdiag.diagnose_pump_plant(diagnoses) rolls the per-loop PumpDriftDiagnosis objects into one plant verdict with the cross-pump reasoning: exactly one pump drifting → single-pump (stage the spare, schedule that impeller); two or more loops on the distribution side → a shared/central hydraulic cause (plant-wide low-ΔT, a decoupler bypass, a control problem) is more likely than several independent pumps; two or more pumps otherwise → plant-wide (a common-mode cause — suction, water chemistry, a shared drive). It reports a plant locus (steady · single-pump · distribution · plant-wide) and a plain-language recommendation.

Surfacing the verdict

The per-loop and per-plant verdicts flow downstream like the chiller ones: camber.integrate.export.pump_diagnoses_to_frame / export_pump_diagnoses write one row per loop (locus · severity · loop_wide · corroborated · causes · fingerprint) to CSV/JSON/Parquet, and camber.report.pump_diagnosis_table renders a worst-first HTML table. build_site_report(..., pump_diagnoses=[...]) splices that table into the owner-facing site report, alongside the chiller verdict table.

Running the family

From a config, no Python needed — add a drift section naming this family ("family": "pump") and run camber drift freeze once to establish the references, then camber drift run to score. camber run folds the verdicts into the ordinary audit report. Only freeze (and the attributed accept_new_normal) ever writes a baseline; scoring is read-only. See CLI.md.

camber drift freeze config.json      # establish the references (refuses to overwrite)
camber drift run    config.json      # score current vs baseline, worst-first
camber drift accept config.json --equip <EQ> --by <NAME> --reason "<what changed>"

Hot-water loops

The pump family reads the chilled-water roles. Since 0.105 (#152) the hw_pump family runs the same five detectors on a hot-water loop (camber.rules.hw_pump_rules):

Detector Rule name Signal Normalizer
HwPumpFlowDrift hw_pump_flow_drift hw_flow hw_pump_speed (or pump_status); hw_diff_press / hw_diff_press_sp for the resistance caveat
HwPumpHeadDrift hw_pump_head_drift pump_head hw_pump_speed (or pump_status); hw_flow confound
HwLoopDeltaTDrift hw_loop_deltat_drift supply − return (hw_supply_temp − hw_return_temp) hw_flow
HwLoopDPDrift hw_loop_dp_drift hw_diff_press hw_flow; hw_diff_press_sp
HwPumpPowerDrift hw_pump_power_drift power hw_flow

A hot-water loop's warm side is its supply, so the ΔT is supply − return. A collapse is still low-ΔT syndrome and a widening is still starvation. The physics, the size-relative gates, the thresholds and the metric keys are the chilled-water detector's own. diagnose_pump_drift and the plant roll-up read either loop, and "plant" works on an hw_pump entry too:

{"drift": {"families": [{"class": "HW_PLANT", "family": "hw_pump", "plant": "HW plant"}]}}

Two loops on one equipment. Each hot-water detector has its own rule name and its own baseline-store kind (hw_pump_flow, hw_pump_head, hw_loop_deltat, hw_loop_dp, hw_pump_power). An equipment that carries both loops, with pump and hw_pump entries on the same class, keeps one frozen baseline per loop. pump_status, pump_head and power have no loop of their own, so on such an equipment both families read the same point. Map each pump as its own equipment when each has its own status, head and power.

A hot-water loop with no flow meter can still be scored on ΔT from Python: HwLoopDeltaTDrift(store, load_role=Role.HW_PUMP_SPEED) uses the pump speed as the affinity proxy, gated at the learned VFD floor.

On lbnl-boiler. Run with the fault-free run as the declared reference, over all 17 runs. The dataset maps the lead pump's speed and status, boiler 1's flow, the loop supply and return temperatures and the loop DP and its setpoint. It has no pump head point, and the pump power point is not mapped. - Pump speed gate: the lead pump's learned VFD floor is 28.9 %, so its speed gate is 30.9 %. - hw_loop_deltat_drift: the PI-mistuning run is a warn, a ΔT collapse of 1.6 °F (3.0σ). The eight temperature-bias runs are faults of 3.6 °F (±2 °F bias) and 7.2 °F (±4 °F bias), collapsing for a positive bias and widening for a negative one. The boiler supply bias moves the loop supply it controls, and the loop sensor bias moves the measured ΔT. The detector cannot tell a biased temperature sensor from a real change in ΔT. The three fouling runs and the four DP-sensor-bias runs are ok. - hw_pump_flow_drift and hw_loop_dp_drift: ok on every run. The largest flow shift is a −22 gpm deficit (−1.9σ) at the −20 DP-sensor bias. - hw_pump_head_drift: declines (no head point).

None of these runs is a pump fault, and boiler fouling stays the job of boiler_efficiency_drift. The lbnl-boiler run template does not include hw_pump, so its workbook answers are unchanged.

Pump size and constant-speed pumps

Until 0.104 the detectors gated on fixed numbers: 50 gpm of flow, a 15 % speed, a 15 / 30 gpm flow deficit and a 1 / 2 kW power excess. A 40 gpm pump never reaches 50 gpm, so the loop ΔT, loop DP and pump-power detectors declined on it, and a worn impeller's whole deficit sat under the 15 gpm floor. Since 0.104 (#150) each gate is derived from the baseline period, capped at the old value, and an explicit constructor value always wins (camber.rules._pumpgates):

Gate Default Cap (pumps at or above it gated as before)
minimum flow / identifiable flow span 10 % / 20 % of the baseline's p95 flow (size_relative_load_gates, as the chiller rules since 0.84) 50 / 10 gpm (500 gpm)
minimum speed the learned VFD floor (camber.chwpump.learn_vfd_floor) + 2 points, else 15 % none: speed is already relative
flow-deficit floor (pump_flow_drift) 2 % / 4 % of the baseline's p95 flow 15 / 30 gpm (750 gpm)
power-excess floor (pump_power_drift) 5.5 % / 11 % of the baseline's p95 power 1 / 2 kW (18.2 kW)
flow-rise confound (pump_head_drift) 2.5 % of the baseline's p95 flow 20 gpm (800 gpm)

The speed gate leaves out the samples a pump spends parked at its drive minimum: there the drive, not the load, sets the speed, so they say nothing about flow or head at a speed. loop_deltat_drift uses the speed gate too when a pump speed stands in for flow (it used 50).

The sigma floors still carry the weight. The gpm and kW floors are backstops against a very tight baseline. On the original 1000 gpm pump (p95 983–993 gpm, 19.7–19.9 kW) the old floors were 1.5 % of flow and 5.1 % of power, so any larger fraction leaves every full-size result unchanged. Within that bound: - Flow: the sigma floor binds first for every fraction from 1.6 % to 3 % at every size, so 2 % / 4 % keeps the backstop at or above typical flow-meter accuracy. - Power: the kW floor does bind on small pumps. At 6 % a small pump catches bearing drag 0.125–0.25 severity later than the full-size pump; 5.5 % keeps it within 0.125.

Head, loop DP and ΔT are pressures and a temperature difference, so their floors do not scale.

Constant-speed pumps have no speed curve to normalize on. pump_flow_drift and pump_head_drift treat a pump as constant-speed in two cases: - its speed varies by at most 2 % (coefficient of variation over the baseline, constant_speed_cv); - it has no speed point but has a running status. The two detectors now run on a speed point or a status.

Instead of declining, such a pump's flow and head are compared as a flat level at its fixed speed, inside the band they were observed at. The Finding carries a caveat that a level change is pump wear or a change in the system curve: a throttled or re-set balancing valve moves a constant-speed pump back along its curve just as wear does. The flow detector's rising-DP resistance caveat still applies.

In the same way, a loop whose flow barely moves (constant_cv, 2 %) gets a flat-level baseline in loop_deltat_drift, loop_dp_drift and pump_power_drift, valid within 5 % of its median flow beyond the observed band. A current period outside that band is not scored. Each Finding reports the gates and floors it used: - *_speed_gate_pct / *_load_gate; - *_gate_source: explicit, size_relative, learned_vfd_floor or default; - *_vfd_floor_pct and *_warn_floor_*; - *_speed_mode / *_normalizer_mode; - *_baseline_model.

The size sweep. camber.pumpsim takes design_flow_gpm, which scales flow, power and their noise, plus fixed_speed and speed_point=False. The sweep runs every fault at severities 2–4 (2 seeds each) and 10 healthy plus 6 DP-reset runs per size. Each cell is the number of cases the detector flagged (warn or fault), 0.103 → 0.104.

Variable-speed pump:

Pump (gpm) Flow faults (pump_flow_drift) Head (pump_head_drift) Bearing drag (pump_power_drift) ΔT faults (loop_deltat_drift) DP faults (loop_dp_drift) Locus right False alarms
20 0 → 24 of 24 18 → 18 of 18 0 → 6 of 6 0 → 10 of 12 0 → 11 of 12 24 → 47 of 48 0 → 0 of 18
40 0 → 24 of 24 18 → 18 of 18 0 → 6 of 6 0 → 10 of 12 0 → 11 of 12 24 → 47 of 48 0 → 0 of 18
100 0 → 24 of 24 18 → 18 of 18 0 → 6 of 6 10 → 10 of 12 11 → 11 of 12 41 → 47 of 48 0 → 0 of 18
200 8 → 24 of 24 18 → 18 of 18 0 → 6 of 6 10 → 10 of 12 11 → 11 of 12 41 → 47 of 48 0 → 0 of 18
500 24 → 24 of 24 18 → 18 of 18 4 → 6 of 6 10 → 10 of 12 11 → 11 of 12 45 → 47 of 48 0 → 0 of 18
1000 24 → 24 of 24 18 → 18 of 18 6 → 6 of 6 10 → 10 of 12 11 → 11 of 12 47 → 47 of 48 0 → 0 of 18

Every size now detects and localizes what the 1000 gpm pump does. The 1000 gpm results are unchanged: tests/golden/pumpsim_fullsize.json, captured at 0.103, pins them. The cases still missed are the same at every size: valve-authority loss at severity 2 for loop ΔT, and one severity-2 case for loop DP.

Constant-speed pump (the same at every size from 20 to 1000 gpm; a status-only pump with no speed point reads the same):

Detector 0.103 0.104
Flow faults (pump_flow_drift) declined 24 of 24
Head (pump_head_drift) declined 18 of 18
Bearing drag, ΔT, DP declined below 500 / 200 / 200 gpm 6 of 6, 10 of 12, 10 of 12
Locus right 6 to 29 of 48 45 of 48
False alarms 0 of 18 0 of 18

A constant-speed pump cannot change its flow by more than the system curve allows, so the sim's severity-4 faults that move flow by 8 to 14 % leave the flat level's band. The loop detectors then decline those samples rather than score them. The one place the flat level misleads is severity-4 overpumping (+8 % flow at fixed speed). There, the extra power the extra flow draws reads as an efficiency loss, and the loop reads loop-wide instead of distribution in 2 of 6 cases.

Calibration

Thresholds are constructor arguments (screening-grade); the CUSUM parameters are provisional-untuned. As with the chiller family, camber.driftvalidation (LabeledCase / evaluate / sweep) tunes them once labelled pump-fault periods exist, and the physics generator camber.pumpsim (affinity laws + system curve) characterizes the family end-to-end without a dataset — on clear faults the loop diagnosis localizes to the right locus at ~100% with no false alarms on healthy loops or a DP-reset schedule, and it proves the flow-vs-head disambiguation (impeller wear → pump, clogged strainer → distribution).