Every BAS export tool formats trend data differently, and there is no public archive of raw per-vendor exports to test against (they're proprietary and site-specific). So CAMBER handles the variety directly: two shared parsers swallow the common timestamp/value encodings, and named vendor profiles capture each tool's documented CSV conventions. All ingest adapters share these, so a new format is handled once, everywhere.

flowchart LR
  export["BAS CSV export"]
  profile["IngestProfile (delimiter, tz, separators)"]
  wide["WideCsvAdapter"]
  perpoint["PerPointCsvAdapter"]
  long["LongCsvAdapter"]
  ts["parse_timestamps"]
  coerce["coerce_numeric / coerce_status"]
  frame["standard wide frame"]
  export -- "load_csv(profile=...)" --> profile
  profile --> wide
  profile --> perpoint
  profile --> long
  wide --> ts
  perpoint --> ts
  long --> ts
  ts --> coerce
  coerce --> frame

A vendor profile selects the CSV shape; the shared parsers normalize every variant to one frame.

Timestamps — camber.tsparse.parse_timestamps

One parser behind every adapter. It strips a trailing timezone abbreviation (PDT/GMT — but not an AM/PM meridiem), tries an ordered list of explicit formats (the common BAS/ISO ones first, so existing data parses identically), detects epoch (seconds/millis) and Excel serial numbers, and falls back to pandas inference last. It never raises — unparseable entries become NaT.

Handled out of the box: ISO 8601 (incl. offsets), US MM/DD/YYYY (12- and 24-hour), European DD/MM/YYYY (dayfirst=True), the BAS 21-Apr-23 8:30:03 AM PDT, LBNL yyyymmdd hh:mm, epoch seconds/millis, and Excel serial dates. Naive-local by default (CAMBER's downstream convention); tz is preserved only with naive=False/assume_tz. Two silent traps are now fixed: European 03/04/2025 (was read as US March 4) and a non-BAS per-point format (previously yielded a silently empty series).

Data types — camber.coerce

  • coerce_numeric normalizes a null/quality-token vocabulary (N/A, ---, Bad, Comm Fail, …) to NaN and strips thousands separators / a European decimal comma before to_numeric — so a stray text cell can't poison a column and grouped numbers (1,234) parse. Clean numerics are unchanged.
  • coerce_status maps status/command text to 0/1 with an extensible vocabulary: On/Off, Running/Stopped, Open/Closed, Fault/Alarm/Normal, Override/Hand/Manual, Auto, plus a numeric-nonzero fallback. Used for the STATUS_ROLES.

Vendor profiles — camber.ingest.profiles

An IngestProfile captures a tool's delimiter, encoding, header rows to skip, timestamp format, day-first flag, and decimal/thousands separators. Named presets (starting points from public vendor docs; every field overridable):

Profile Convention
generic (default) comma, UTF-8 (BOM-tolerant), auto-detect timestamp
niagara_n4 Tridium Niagara N4 history export — BAS 12-hour timestamp
metasys JCI Metasys — US month-first 12-hour
webctrl Automated Logic WebCTRL — US month-first
tracer Trane Tracer — ISO-ish
desigo Siemens Desigo (European) — semicolon, decimal comma, DD.MM.YYYY, day-first
from camber.io import load_csv

load_csv("export.csv", profile="desigo")  # semicolon + decimal comma + DD.MM.YYYY
load_csv("export.csv", profile="metasys", skiprows=2)  # skip a 2-row export preamble
load_csv("export.csv", delimiter="|", dayfirst=True)  # or override fields directly

Profiles thread through io.load_csv and WideCsvAdapter; defaults resolve to generic (fully backward compatible).

CSV shapes

  • Wide — io.load_csv / WideCsvAdapter: one timestamp column + one column per point.
  • Per-point — PerPointCsvAdapter: a folder of <name>.csv, each Timestamp,Value(<unit>).
  • Long/tall — LongCsvAdapter (new): one row per timestamp,point,value[,unit] (the historian export shape), pivoted to the standard wide frame.

Guarantee

A synthetic per-vendor corpus (tests/test_ingest_formats.py) writes the same data in each vendor's format and asserts they all normalize to the identical frame — the equivalence proof, since a raw per-vendor archive can't be published. See INGEST-PROTOCOLS.md for the read-only network adapters (Modbus/MQTT/BACnet/OPC-UA), which share these same parsers.