Network ingest protocols
CAMBER's primary ingest path is the historian / SQL / Haystack tier (see SECURITY.md). For sites where direct acquisition is required, it also ships read-only network adapters for Modbus, MQTT, and BACnet. Each:
- implements the
SourceAdaptershape (point_names()/load_points()/units()), - imports its protocol library lazily behind an optional extra (the core stays dependency-light), and
- is read-only by construction — it references no write/command service (enforced by test).
flowchart LR
modbus["ModbusSource (modbus)"]
mqtt["MqttStreamSource (mqtt)"]
bacnet["BacnetSource (bacnet)"]
opcua["OpcUaSource (opcua)"]
sql["SqlSource"]
haystack["HaystackAdapter"]
csv["WideCsvAdapter"]
proto["SourceAdapter protocol"]
frame["role-frame"]
modbus -- implements --> proto
mqtt -- implements --> proto
bacnet -- implements --> proto
opcua -- implements --> proto
sql -- implements --> proto
haystack -- implements --> proto
csv -- implements --> proto
proto -- "point_names / load_points / units" --> frame
Every protocol adapter satisfies the same read-only SourceAdapter shape and fans into one role-frame.
| Protocol | Module | Extra | Library | License | Shape |
|---|---|---|---|---|---|
| Modbus TCP | camber.ingest.modbus |
[modbus] |
pymodbus | BSD-3 | snapshot / poll |
| MQTT (+ Sparkplug) | camber.ingest.mqtt_stream |
[mqtt] |
paho-mqtt | EDL-1.0 / EPL-2.0 | streaming buffer |
| BACnet (+ SC) | camber.ingest.bacnet |
[bacnet] |
bacpypes3 | MIT | Trend-Log / present value |
| OPC-UA | camber.ingest.opcua |
[opcua] |
asyncua | LGPL-3.0 † | history / current value |
† asyncua is LGPL-3.0 — kept as an optional, dynamically-imported dependency only (never vendored/bundled), so CAMBER's own code stays Apache-2.0.
pip install "camber-toolkit[modbus]" # or [mqtt], [bacnet], [opcua]
Modbus — camber.ingest.modbus
Modbus has no history: a read returns the current register. ModbusSource.read_snapshot()
reads each mapped ModbusPoint (holding/input register, slave id, 16- or 32-bit, scale/offset);
poll() samples repeatedly into a short series; load_points() returns a one-row snapshot. For
long trends use a historian. Modbus has no authentication or encryption — keep the host out
of the control VLAN. The client is injectable (pymodbus-style read_holding_registers /
read_input_registers) for testing.
MQTT — camber.ingest.mqtt_stream
MQTT is push. MqttStreamSource.subscribe() connects (TLS via tls=True), subscribes to the
mapped topics, and routes each message into the pure ingest() handler, which parses the payload
(a bare value, or a JSON field via value_key — including Sparkplug-B metric fields) and buffers
a timestamped sample. to_frame() / load_points() shape the buffer into per-point series. The
adapter only subscribes; it never publishes.
BACnet — camber.ingest.bacnet
The analytics-friendly BACnet source is a Trend Log object, which already holds timestamped
records; BacnetSource.read_trend_log() / load_points() shape them into series, and
read_snapshot() reads present values. The adapter uses only read services
(READ_SERVICES = ReadProperty, ReadPropertyMultiple, ReadRange).
A trend log is a ring buffer whose position 1 is its oldest record. Since 0.108 (#243) the
bacpypes3 client reads record-count first and then the newest trend_records records (1000 by
default; Bacpypes3Client(trend_records=N), BacnetClientConfig.trend_records, or
read_trend_log(oid, max_records=N)), so a polling forwarder always sees the latest data. A
device that does not answer record-count is read from position 1, as before, with a warning.
Each BacnetPoint can carry its device's device_instance and address (0.108, #248): such a
point is read at its own device, and BacnetSource refuses two points with one name.
BACnet/SC (Secure Connect) — experimental, certificate-gated
Legacy BACnet/IP is UDP, cleartext, broadcast-based, and unauthenticated. BACnet/SC
(ANSI/ASHRAE Addendum 135-2016bj, now in ASHRAE 135) replaces that datalink with secure
WebSockets (wss:// over TLS 1.3), a hub-and-spoke topology (no broadcasts), and mutual X.509
certificate authentication. BacnetTarget(secure=True, hub_uri=…, cert=…, key=…, ca=…) carries
the SC config and validate() rejects an incomplete one.
Two honesty caveats, both deliberate:
- Joining an SC network requires an operational certificate issued for that network plus the hub URI — there is no IP-only path. This is an administrative onboarding step CAMBER cannot ship around.
- Production-grade SC mutual-auth in the open-source Python stack (bacpypes3) is still
maturing. bacpypes3 (MIT, actively maintained) has SC code and ships
websocketsas an extra, but its own docs describe SC as in development. So CAMBER's claim is deliberately scoped: BACnet/SC-capable (experimental), not an unqualified "BACnet/SC compatible."
Accordingly, the default BACnet client is not auto-constructed: BacnetSource expects an
injected client exposing read_trend_log(object_id) and read_present_value(object_id) (a thin
bacpypes3 wrapper configured per deployment), or — recommended for production — reach BACnet data
through a historian/gateway that already speaks SC on the OT side and read it via the SQL or
Haystack adapter.
Discovery — camber.ingest.bacnet_discovery
The read adapter above reads a point list you already have; discovery builds that list.
discover(client) enumerates a network read-only — Who-Is / I-Am for devices, then ReadProperty
object-list and ReadPropertyMultiple of descriptive properties (object-name, units,
description) per object — and returns DiscoveredDevice / DiscoveredObject records. Its service
and property allowlists (DISCOVERY_SERVICES, DISCOVERY_READ_PROPERTIES) are asserted read-only by
the same AST guard as the read adapter; there is no write path.
Like BacnetSource, the network I/O is an injected DiscoveryClient (core builds no bacpypes3
app), so discovery is testable without a network. A deployment implements three read methods
(who_is, read_object_list, read_object_metadata) over bacpypes3:
from camber.ingest.bacnet_discovery import discover, discovery_to_points, discovery_to_inventory
from camber.interop.bacnet import mapping_from_bacnet, review_bacnet
devices = discover(my_client) # read-only enumeration
points = discovery_to_points(devices) # Trend-Log objects -> BacnetPoint (feed BacnetSource)
# each point names its device (instance, address); objects that share a name on different
# devices are named "<device name>_<object name>" (0.108, #248), with a UserWarning
rows = discovery_to_inventory(devices) # a flat per-object inventory
objs = [o for d in devices for o in d.objects]
mapping = mapping_from_bacnet(objs) # bootstrap a point -> Role mapping
review = review_bacnet(objs, mapping) # advisory suggestions for the rest
The mapping bridges each object's name, object type, and engineering units to a
vendor-neutral Role, reusing the assisted-mapping suggester (camber.mapping_assist). It is a
bootstrap for operator review, never an unattended remap.
Vendor proprietary properties (camber.interop.bacnet_vendor, [bacnet-vendor]). Real vendor
devices expose proprietary properties (identifiers ≥512) a generic stack can't decode. The optional
bridge to ace-bacnet-devices (MIT) supplies
typed decoders: call install_vendor_decoders() when you build the bacpypes3 client — registration
only affects the app it runs on, so it can't retroactively re-decode an app built without it — and
proprietary reads come back typed. Its catalog also feeds mapping hints (vendor_hint_tokens /
vendor_aliases), where vendor_aliases is deliberately strict so it never silently mis-maps a point.
Default client (camber.ingest.bacnet_client) — bacpypes3, read-only
Rather than hand-write the DiscoveryClient / read client, use the bundled bacpypes3-backed default
(the [bacnet] extra). It's a read-only sync facade — it only ever calls who_is /
read_property / read_property_multiple / read_range (asserted by the ingest read-only AST guard)
— and implements both roles:
from camber.ingest.bacnet import BacnetSource, BacnetPoint, BacnetTarget
from camber.ingest.bacnet_client import BacnetClientConfig, bacnet_read_client, discover_default
cfg = BacnetClientConfig(local_address="0.0.0.0/24:47808", device_range=(1, 4194303))
devices = discover_default(cfg) # discover a network -> bootstrap a mapping
target = BacnetTarget(address="10.0.0.5") # then read a known device's Trend Logs
src = BacnetSource(
[BacnetPoint("SAT", ("trendLog", 3))], target, client=bacnet_read_client(target, cfg)
)
df = src.load_points(["SAT"])
Configure it three equivalent ways — the API (BacnetClientConfig(...)), a YAML/JSON file
(BacnetClientConfig.from_file("bacnet.yml")), or the CLI (camber bacnet-discover --config
bacnet.yml). A YAML config:
local_address: "0.0.0.0/24:47808" # interface/IP[:port] to bind (multi-homed host / BBMD)
local_device_id: 599 # this host's BACnet device instance
local_object_name: camber
vendor_id: 555
timeout: 10.0
device_range: [1, 4194303] # Who-Is device-instance window
Segmented / cloud networks: broadcast Who-Is doesn't cross subnets without a BBMD, so set
known_addresses (config) / --device <addr> (CLI, repeatable) to enumerate specific devices by a
directed (unicast) Who-Is instead — discover_default uses discover_addresses automatically when
addresses are given.
Caveats (best-effort, by design): one Application per process (it binds the BACnet UDP port); on
a multi-homed host pin local_address, and register with a BBMD for cross-subnet broadcast Who-Is;
bacpypes3 is upstream Pre-Alpha (0.0.x) and BACnet/SC is experimental. Only the injected-client
seam is unit-tested — the live client is validated against a simulated device, not in CI — so the
historian / SQL / Haystack path stays recommended for production.
OPC-UA — camber.ingest.opcua
The analytics-friendly OPC-UA source is a historizing node, whose retained timestamped values
map onto a series; OpcUaSource.read_history() / load_points(start=…, end=…) shape them, and
read_snapshot() (or load_points() with no window) reads current values. The adapter uses only
the read services (READ_SERVICES = Read, HistoryRead).
OPC-UA is secure-by-design: pass an OpcUaSecurity with asyncua's security string (policy, mode,
client cert/key) and/or username/password, and connect to an encrypted, authenticated endpoint —
not a None-security one — on a production network. The client is injectable (any object with
read_value(node_id) and read_history(node_id, start, end)); the default wraps asyncua's
synchronous client and needs a url.
Licensing: asyncua is LGPL-3.0, so it is an optional, dynamically-imported dependency only — never vendored or statically bundled — which keeps CAMBER's own code Apache-2.0.
Other protocols considered
- VOLTTRON (Eclipse, Apache-2.0) — a full ZMQ/gevent agent platform, not a light library; its BACnet driver even needs a separate proxy process. CAMBER treats VOLTTRON as a data source (point the SQL adapter at its SQLite/PostgreSQL historian, or the MQTT adapter at forwarded telemetry) and a design reference — not a dependency. See ECOSYSTEM.md.
References
- ASHRAE Addendum 135-2016bj — https://www.ashrae.org/File%20Library/Technical%20Resources/Standards%20and%20Guidelines/Standards%20Addenda/135_2016_bj_20191118.pdf
- BACnet International — BACnet/SC — https://bacnetinternational.org/bacnetsc/
- How Digital Certificates are Used in BACnet/SC — https://www.automatedbuildings.com/2026/02/how-digital-certificates-are-used-in-bacnet-sc/
- bacpypes3 — https://github.com/JoelBender/BACpypes3 · pymodbus — https://www.pymodbus.org/ · paho-mqtt — https://github.com/eclipse-paho/paho.mqtt.python