Validation & methods

How CAMBER's results are kept honest and checkable. The project's promise is defensible, citable analytics, so every layer is validated against a public standard, an independent implementation, or labeled ground truth — and uncertainty is reported, not hidden.

flowchart LR
    synth["synthetic faults (camber.faultlab)"] --> ev["camber.eval (confusion, TPR/FPR)"]
    lbnl["real LBNL FDD data"] --> ev
    bdg2["real BDG2 meters (G14 acceptance)"] --> mv["M&V acceptance rate"]
    ev --> ci["metrics_with_ci (Wilson CI)"]
    mv --> ci
    ci --> gate["check_against_baseline (CI gate)"]
    gate --> report["published accuracy"]

Synthetic and real (LBNL, BDG2) benchmarks flow through the eval framework into CI-reported accuracy with confidence intervals and a baseline gate.

Principles

  • Clean-room & citable. Every method cites a public standard (ASHRAE G36/G14/Std-55/ Std-211, IPMVP, PNNL Building Re-tuning, NIST APAR, CalTRACK); no proprietary code or text. Each rule ships a synthetic fixture that proves detection.
  • Honest results. Report uncertainty and limitations; never overstate a fit or a saving.
  • Reproducible. Deterministic synthetic fixtures; camber.validation.check_determinism asserts a function returns identical output across runs; CI runs the suite on Python 3.10 and 3.11.

FDD accuracy — labeled public datasets

camber.eval implements the LBNL FDD performance-evaluation framework (confusion matrix, TPR/FPR/accuracy, correct-diagnosis rate). examples/lbnl_fdd/benchmark.py scores the detector suite across three LBNL equipment families (single-duct AHU, fan-coil unit, dual-duct AHU — CC-BY labeled data) and now reports each rate with a 95% Wilson score confidence interval (camber.validation.metrics_with_ci), because per-family samples are small and a bare percentage would overstate certainty.

Representative result (OA-fraction detector vs stuck dampers):

Set TPR (95% CI) FPR n
SDAHU 50% [15–85%] 0% 6
FCU 100% [44–100%] 0% 4
DDAHU 100% [34–100%] 0% 3
Pooled 78% [45–94%] 0% 13

The honest read the CIs force: judged on fan-on, occupied samples against each unit's own design minimum, OA-fraction catches every stuck damper on the fan-coil and dual-duct units with no false alarm, but on the single-duct AHU it catches only the dampers stuck well open (75 %, 100 %). A damper stuck at that unit's 10 % minimum, or at 25 % (4.4 % OA against a 1.6 % minimum), looks like normal ventilation outside economizer weather; its real symptom is the missed economizer, which economizer_damper_drift catches (below). leaking_valve catches the dataset's one leak run — a 10 % leak (the valve sits at 0.10 whenever it is commanded shut; the published 010/025/040/050 "severities" are one file) — since 0.98 (#84), but only with a fan heat calibrated on this unit: see the circularity note below. The benchmark measures these gaps rather than hides them. The pooled interval is the defensible headline; the small-n per-family numbers are reported with their uncertainty.

These figures moved in 0.86 (#30). The 0.85 table read SDAHU 100 %, DDAHU 50 % with an FPR of 100 %, and pooled 89 % [56–98 %] with an FPR of 25 %. The 0.86 catalog audit (#24–#29) found that those figures rested on CAMBER's own wrong assumptions: a 20 % minimum OA for a single-duct unit whose design minimum is a 10 % damper position (a 1.6 % OA fraction — its "ok" held only because fan-off samples were judged), a flat 20 % for a dual-duct unit whose minimum is seasonal (11.9 % Jun–Aug, 31.8 % otherwise — the source of its FPR of 1.0), and mis-mapped fan and occupancy points. With the fixes, outdoor_air_fraction judges fan-on, occupied samples against each unit's own minimum, so the SDAHU TPR fell and the dual-duct FPR fell to 0. The gated baseline (examples/lbnl_fdd/benchmark-baseline.json) was refreshed with the maintainer's sign-off; the CHANGELOG lists every gated metric that moved. Every published-data problem is listed with its evidence in DATASETS.md.

The FCU result is fragile. Its OA-damper leak runs give 12.7 / 15.4 / 17.4 % OA (20 / 50 / 80 % leakage) against the rule's 15 % excess line (the unit's 10 % minimum + 5 %): the leak-50 detection the benchmark scores rests on a 0.4-point margin.

Drift-family real-data validation (which detectors the data can honestly test)

The newer drift and Trim-and-Respond reset families are only partly validatable on the public datasets we have, and examples/lbnl_fdd/benchmark.py now scores exactly what the LBNL SDAHU data can support (via camber.driftvalidation.evaluate: baseline = fault-free run, current = a labeled fault run):

Declined cases (the detector could not test its claim) are excluded from the score and counted separately — DetectorScore.n_declined; scoring them would credit a specificity the detector never demonstrated. A detector's positives are the faults its documented physics says it sees; the one-sided drift detectors do not claim opposite-direction faults (a leak lowers the valve demand), so those score as cross-negatives. Valves and dampers are read from the dataset's controller-demand columns (*_DM), which is how CAMBER's rules interpret those roles. The SDAHU numbers are gated in CI by examples/lbnl_fdd/benchmark-baseline.json.

Detector On LBNL SDAHU Why
coil_valve_drift specificity only — 1 false alarm in 6 one-sided up (fouling / waterside starvation / authority loss), none of which the SDAHU set labels; its coil-valve leak is the opposite direction (the leak delivers cooling the controller didn't ask for, so the demand falls) and is leaking_valve's job, so it scores as a cross-negative. The false alarm is the damper stuck at 100%: hot outdoor air adds latent coil load a sensible air-ΔT cannot see (+9%, 2.6σ) — the documented latent confound
economizer_damper_drift recall 4/4, 0 false positives in 2 (11–17σ) read against the damper command (OA_DMPR_DM). Against the measured position — what this benchmark mapped until 0.82.0 — a stuck damper's OA fraction matches its (stuck) position and the fault is invisible: recall 0/4
duct_static_drift not measured — declines all 6 cases no labeled duct-static fault in the fetched set, and the baseline period will not support a static-vs-airflow fit, so there is no specificity number either. Until 0.82.0 those declines were booked as true negatives and reported as FPR 0.0
fan_efficiency_drift, filter_loading_drift synthetic-only need POWER / FILTER_DIFF_PRESS points the SDAHU simulation does not export
vav_airflow_drift, vav_reheat_valve_drift measured on the LBNL FPU subset, parallel boxes (PFPU) (opt-in fetch.py --fpu, not gated in CI): airflow recall 5/5, 0 false positives in 24; reheat valve recall 2/8, 0 false positives in 17, 3 declined the faults are imposed on the South box (_S); until 0.82.0 the mapping pointed at the healthy West box and both detectors scored 0. The target lists follow each rule's documented physics (revised in 0.92.0; before, airflow scored 4/6 and reheat 1/7 on older lists). Both rules are one-sided up. Airflow targets the dampers stuck at 50 / 80 / 100 % and the low-reading (−200 / −400 CFM) flow sensor, and catches all five. The dampers stuck at 0 % and 20 % drift down (56σ and 4σ), outside its one-sided claim, so they are excluded rather than scored either way. Its cross-negatives, where it rightly stays silent, are the high-reading sensor (+200 / +400 CFM), damper instability, fan restriction, the room-temperature faults and every reheat fault. Reheat targets the valve stuck at 0 % and 20 % (read from the valve demand RH_VLV_DM_S) and all six air- and water-side coil-fouling runs. It catches both stuck valves and misses every fouling run (within 0.03σ): fouling leaves no trace in the box's trended points, since valve demand, discharge temperature and HW flow medians are identical to the fault-free run. Its cross-negatives are the valves stuck at 50–100 % or leaking (they over-deliver, so the demand falls), the stuck dampers and the airflow and room-temperature sensor biases. It declines the high-reading airflow-sensor runs and the damper stuck at 0 %. The instability and fan-restriction runs are excluded, because the rule's physics predicts nothing for them. The counts come from examples/lbnl_fdd/optin-measured.json (the last opt-in run), which a test checks this row against
series-box (SFPU) vav_airflow_drift, vav_reheat_valve_drift measured on the LBNL FPU subset, series boxes (SFPU) (opt-in, not gated; scored since 0.92.0 against SFPU_FaultFree, same target lists): airflow recall 5/5, 4 false positives in 24; reheat valve recall 2/8, 4 false positives in 14, 6 declined before 0.92.0 no series run was scored at all. In a series box the fan pulls primary and plenum air through the reheat coil, so the reheat duty reads the fan discharge flow (VAV_DA_CFM_S) instead of the primary flow; the airflow rule still reads the damper against the primary-flow command. Airflow's four false alarms are the reheat valves leaking at 50 % / 80 % and stuck at 80 % / 100 %: the overheated room drives the primary-flow command far above anything in the baseline (up to 1,000 cfm against a fault-free p95 of about 450), so the damper is judged by extrapolation. Physically the damper is healthy there, so they are counted as false positives. Reheat catches the valves stuck at 0 % and 20 % and misses all six fouling runs, as on the parallel box. Its false alarms are the room-temperature biases +2 / +4 °C and the dampers stuck at 80 % / 100 %. The coil's entering air is a primary/plenum mix that no point measures (the AHU supply temperature is the proxy), so a warmer room or a changed primary share reads as creep. With the primary flow as the duty instead, reheat scores 2/8 with 3 false positives in 11 (the damper stuck at 20 % instead of 80 / 100 %), and declines 9 runs. The discharge flow is kept because it is the coil's physical airflow, not because of the score. Counts from examples/lbnl_fdd/optin-measured.json
chiller_efficiency, cooling_tower_approach measured on the LBNL chiller-plant subset (opt-in fetch.py --chiller, not gated in CI): chiller_efficiency TPR 6/11, FPR 2/13; cooling_tower_approach TPR 0/3, FPR 0/14, 7 declined kW/ton catches every condenser-bypass-valve fault and the severe chiller fouling (065, 2.36 kW/ton against the 1.44 calibration; the archive's undocumented chiller-fouling runs are positives since 0.86) and misses tower fouling / PI mistuning (≤ 7% kW/ton change) and the mild chiller fouling (095, 1.53); its false alarms are the two positive chiller sensor-bias runs, whose biased temperature corrupts the tonnage. Since 0.92.0 the three sensor-bias families (chiller and tower leaving water ±1 / ±2 °C, secondary-loop DP ±10 / ±20 %) are listed as negatives for both rules, and so are the chiller-fouling and bypass runs for the tower rule; a run on no list is excluded, where before every non-target run was a negative by default. No count moved. The tower rule never ran before 0.82.0 (a 0–1 fan speed was never rescaled; the exported wet-bulb and dry-bulb columns are swapped — see the lbnl-chiller catalog entry's fix quirk and camber/datasets/mappings/lbnl_chiller.json). It now judges approach only at high fan effort (≥ 90%): the plant holds a 60 °F minimum condenser-water temperature, so in cold weather a healthy tower sits far above wet-bulb + design with its fan idling — which fired the rule on all five bypass-valve runs (a leaking bypass keeps the tower running all winter). Those, and the PI run, now decline: the tower is never pushed hard, so there is nothing to judge. The −2 °F tower-sensor-bias run declines too: only 8 samples at ≥ 90 % fan pass the plausibility checks. Fouling is visible at high fan (20% / 7% / 0% of hours above design + 3 °F at 65% / 80% / 95% capacity, vs 0% healthy; 3.3× the high-fan hours at 65%) but the rule's severity is the median approach, which moves only 8.1 → 9.4 °F — so it stays ok. The fan working harder for the same approach is the stronger fouling signature, and is not yet a detector. The counts come from examples/lbnl_fdd/optin-measured.json, which a test checks this row against
sensor bias vs physical fault on the chiller plant (camber.sensordrift.compare_to_reference) measured on the LBNL chiller-plant subset (opt-in, not gated; since 0.92.0): chiller leaving water TPR 2/4, FPR 0/20; tower leaving water TPR 2/4, FPR 5/20 Each sensor is compared with a reference it must equal while the plant's physics holds. Chiller 1's leaving water (CHL_SW_TEMP_1) must equal the primary supply (CWL_PRI_SW_TEMP) while chiller 1 runs alone. Tower 1's leaving water (CT_SW_TEMP_1) must equal the condenser supply (CDWL_SW_TEMP) while tower 1 runs alone with the bypass valve commanded shut. At the documented 2.0 °F warn threshold the ±2 °C biases read exactly ±3.6 °F and are caught; the ±1 °C biases read ±1.8 °F and are missed (a threshold question, left at the default). The fault-free, fouling, PI and DP-bias runs read 0.00 / −0.05 °F. The tower pair's five false alarms are the bypass-valve runs (−37 to −47 °F). A leaking or stuck valve does not obey its command, so condenser water mixes past the tower while the command reads shut. The reference condition cannot be verified from the command alone. This is the complement of chiller_efficiency, which fires on the chiller-bias runs: the pair separates a lying sensor from a real fault that the kW/ton rule cannot. Counts from examples/lbnl_fdd/optin-measured.json
refrigerant-side chiller drift (*_approach_*, subcooling, superheat), pump drift synthetic-only the LBNL chiller-plant subset is water-side only — it exports no refrigerant-side points (evaporator/condenser approach, subcooling, superheat) and no pump-head/flow trends, so those detectors can't be scored on it
refrigerant-side chiller drift on open lab / field data (not vendored, not CI-gated; measured 0.82.0) NIST residential heat-pump FDD lab data (151 labeled cases: 107 faults — under/overcharge, condenser & evaporator airflow, liquid-line restriction — and 44 held-out no-fault files; loads as-is, 0.7–4.3 t): before all six detectors declined 151/151; after, 0 declined — recall / FPR: subcooling 0.34 / 0.00, superheat 0.22 / 0.00, head pressure 0.32 / 0.00 (0.01 load-only), suction pressure 0.00 / 0.00, approach 0.52 / 0.02, approach CUSUM 0.64 / 0.23 (the lab files are steady-state test points on a synthetic time index, so the temporal claim is weak there). NIST IBAL 5-ton chiller, normal operation (22 days after a 5-day baseline): before 100% declined; after, 0 period false alarms on every detector; sustained-alarm false alarms 5-min / 1-min: approach CUSUM 0.59→0.05 / 0.75→0.15, subcooling 0.50→0.00 / 0.90→0.05, suction 0.00 / 0.40→0.05. A mid-run injected step is caught by the period rule / CUSUM at: head +44 psi 100% / 100%, suction −15 psi 64% (5% load-only) / 100%, superheat +8 °F 45% / 100%, subcooling −3 °F 9% / 82%, condenser approach +3 °F 95%. ORNL CO₂ (R744) supermarket rack (5 fault / negative-control pairs): before all declined (gas-cooler pressures above the 700 psig ceiling; small loads); after all scored with 0 false alarms; the low-temp EEV failure is a superheat fault (+36.7 °F, 7.2σ); the gas-cooler air blockage is not detected — its day was hotter than any baseline day (caveated as extrapolated) and compressor kW, the only load proxy, rises with the blockage itself size-relative load gates + flat-level fallback, physical per-metric ranges, refrigerant-neutral pressure ceilings, a heat-sink / leaving-CHW regressor for head / suction pressure, and a serial-correlation-corrected CUSUM (see CHILLER-DRIFT.md). IBAL's second chiller has no evaporator-entering sensor, so compressor kW stands in for load; its period statistics stay specific (0 false alarms) but its CUSUM still flags 33–62% of summer days, when kW ran outside the spring baseline's envelope — a real sustained shift below the period floor, i.e. a tuning question for the provisional CUSUM parameters, documented rather than tuned
hydronic loop / pump drift on the LBNL boiler-plant FDD set (not vendored) loop_dp_drift now scores (was 4/4 declined); pump_power_drift names the missing metric; hw_pump_dp_reset evaluates the DP-setpoint reset the loop DP is trended in inH₂O (480.5 setpoint), which the former psi-only 0–100 band rejected sample by sample while the caveat blamed "too few loaded samples"; the band is now scaled to the loop's own median. Five runs export pump power as "NAN" strings — the decline now says the power column has no numeric values. The HW pump speed is a 0–1 fraction; the rule rescales it and reports the (flat) DP setpoint it previously claimed but never read. No detection claim is made on the boiler faults
cooling_tower_approach on a pilot wet cooling tower (CIEMAT, ~500 m) message + elevation only only 5 samples reached ≥ 90% fan; the decline said the fan "never reached 90%" and now says what happened. The site is ~500 m up: a derived wet-bulb now takes elevation_ft (median approach 29.1 → 30.0 °F) and a sea-level derivation is caveated
*_reset_effectiveness scored on a generated fleet (TPR + failure-mode attribution) the per-cycle reset-request point is generated from the fleet via G36 Trim-&-Respond, not downloaded; scored on all four failure modes (stuck / not-responding / not-trimming / diverges) for both SAT and static — see camber.fleetlab below
*_rogue_zone_census, *_cohort_starvation scored on a generated labeled fleet (TPR/FPR + correct zone/AHU attribution) a clean-room G36 T&R fleet generator (camber.fleetlab) emits per-zone role-frames + served-by topology + ground-truth labels; no public multi-zone-fleet dataset is vendorable, so the fleet is generated from the public ASHRAE G36 §5.14.8 request logic, not downloaded
dcv_verification, dcv_system_verification real data + physics-simulated a lab room with a known DCV law reads functioning on CO₂, count and presence; three office rooms read functioning on camera counts; an office building with no DCV reads insufficient on every unit (never a false functioning), its 11 CO₂ zones attribute through the Brick chain, and its OA flow sits below the assumed floor in 2–4 % of occupied hours (fan-off days, named "supply fan off while scheduled occupied" since 0.98; the 2020 smoke-mode weeks held OA above it), info under the 10 % fault share; a lecture theatre's 110 fan-off hours at 2000 ppm are a fault; a schedule-driven valve is not credited as DCV. Datasets (all licence-clean, cited by DOI, not vendored) and numbers in VENTILATION.md; the synthetic scenario is faultlab.dcv_sim. No labeled DCV-fault dataset exists, so TPR is established on the one known-law room, not a sample

These are honest boundaries, not oversights: where the data can't support a real-fault score, the family is validated on the synthetic whole-suite harness below (camber.faultlab) and said so here.

BDG2 is meter-level — whole-building energy + weather with no component point trends — so it validates the M&V / forecast / anomaly track (below), not component FDD; the drift/reset detectors' required roles (approach, valve %, damper, requests) simply don't exist in it.

Sibling subsets — wired. The VAV fan-power-unit (FPU) subset is wired (fetch.py --fpu + camber/datasets/mappings/lbnl_fpu.json), scoring vav_airflow_drift and vav_reheat_valve_drift on its labeled per-box faults. The chiller-plant subset is now wired too (fetch.py --chiller + camber/datasets/mappings/lbnl_chiller.json) — the open, simulated chiller FDD source that validates the plant-level chiller detectors and sidesteps a licence-encumbered ASHRAE chiller-FDD dataset. It is water-side only (no refrigerant points), so it scores chiller_efficiency and cooling_tower_approach but not the refrigerant-side chiller-drift family. Because the simulated chiller/tower design curves aren't published, each detector's absolute design ceiling is calibrated from the plant's own fault-free run (commissioning practice) rather than guessed, so the informative number is the TPR on the labeled physical faults; sensor-bias runs act as genuine negatives (the plant is healthy, only a sensor lies). RTU/DDAHU/FCU remain available too.

The other real-BMS AHU/VAV sets are, on inspection, not usable for a commercial toolkit's committed benchmark: the only publicly-downloadable version of the widely-cited Korean large-office AHU set is a reduced sample (all-faulted, two coarse labels, no supply-air setpoint, stacked AHUs — no fault-free baseline to score against), and the multi-building office/auditorium/hospital set is not in the catalog. The simulated RBC/G36 AHU collection (rbc-g36-ahu) is in the catalog but research-only (its archive bundles a third-party folder whose open licence CAMBER cannot vouch for), so its results are not published here. One real, labelled multi-zone VAV cohort is open — ORNL's (below) — but it is small and scores zone symptoms, not the Trim-&-Respond resets, which is why the reset/fleet family is still validated on a generated fleet (next section), exactly as the G36 authors intend the public Trim-&-Respond logic to be reused.

0.92 plant detectors on the LBNL plants

examples/lbnl_fdd/plant_detectors.py scores the three plant detectors on the labelled LBNL boiler plant (17 runs) and chiller plant (24 runs). Each detector's target faults are the positives; the fault-free year, every other physical fault and every sensor bias are negatives. The drift rules freeze their baseline from the fault-free year and score each run as the current period; the bypass rule scores each run on its own. A detection is a warn or fault. These are measured, not gated results (the subsets are opt-in downloads), and with three to five positives the 95 % Wilson intervals are wide: they bound the detectors, they do not rank them.

Detector Target runs TPR (95 % CI) FPR (95 % CI) Notes
boiler_efficiency_drift boiler fouling 065 / 080 / 095 3/3 (0.44-1.00) 0/14 (0.00-0.21) ratio +54 % / +25 % / +5.1 %: the 95 % run clears the 5 % warn floor by 0.1 point. The +2 / +4 F hot-water temperature-bias runs raise the ratio 11 % / 25 % with gas at matched OAT up only 3-5 %, so they are reported as heat-metering problems (info), not fouling
cooling_tower_fan_effort_drift tower fouling 065 / 080 / 095 2/3 (0.21-0.94) 0/21 (0.00-0.15) fan +17.8 / +10.9 / +3.3 %-points at matched range and wet-bulb; the 95 % run stays under the 5-point floor. The +1 / +2 F tower-sensor-bias runs drive the fans harder than 65 % fouling (+29 / +48 points) and are caught by the leaving-water vs condenser-entering cross-check (+1.6 / +3.5 F shifts) and reported as sensor offsets
cooling_tower_approach_drift (for comparison) tower fouling 0/3 (0.00-0.56) 0/21 (0.00-0.15) the controller holds the approach, as #14 found
condenser_bypass_leak bypass leakage 25 / 50 / 75 %, stuck 50 / 75 % 5/5 (0.57-1.00) 0/19 (0.00-0.17) medians 42-62 F with the valve commanded shut vs 0.0-0.04 F on every healthy run. The -2 / +2 F tower-sensor-bias runs (3.6 / -3.1 F) are flat across the condenser range and reported as sensor offsets

The chiller-plant mapping gained CDWL_SW_TEMP -> cond_entering_water_temp and TWV_CTRL -> cw_bypass_valve, the boiler mapping BOI_GAS_CSUM_1 -> gas_input_rate; the catalog entries carry the evidence. The simulated RBC/G36 collection's plant faults were also run locally as a research check; as for every research-only set, its numbers are not published.

The same numbers through a config (0.98). The table above comes from the example script, which freezes each drift baseline from the fault-free year by hand. Since 0.98 a drift family can declare that run as its reference (drift.families[].reference, fitted in memory on every run and never stored; see the CLI guide), so the lbnl-chiller and lbnl-boiler templates score cooling_tower_fan_effort_drift and boiler_efficiency_drift with a plain camber run. The verdicts match the script on every run (checked by tests/test_drift_reference_098.py when the data is present), and the two rules are now the entries' declared targets for camber datasets score: TPR 2/3 and 3/3, no false alarm. The fault-free run declines as the reference, but the scorer still counts it as a correct negative, so its FPR denominators are the 21 and 14 above.

Real labelled multi-zone VAV cohort — ORNL FRP (ornl-frp-vav, CC-BY-4.0)

CAMBER's first result on real, labelled, multi-zone VAV data (0.89): the ORNL Flexible Research Platform, a two-storey test building with one rooftop unit and ten VAV boxes, where a box damper was held stuck at 0 / 20 / 40 / 60 / 80 / 100 % for one day each in three rooms (106 and 104 in August 2023, 205 in December 2023), plus a fault-free day per set, and room 205's airflow reading was biased ±20 / 40 % over two sets of April 2024 days (Im, Jung & Yoon 2025, Sci Data, doi:10.1038/s41597-025-05063-z). Every box is logged, so each test day is a real zone cohort: the box under test is scored and its nine neighbours are unscored context.

Since 0.98 the catalog template declares actuator_stuck as the detector for the stuck dampers: it judges each stretch where a box's damper holds one position against what the room asked for (shut through occupied hours, part open while the room runs warm, fully open while it is satisfied: a fault; held all day while the room temperature moves: a warning, which the score counts as a detection). Until 0.97 it declared unmet_setpoint_hours, the comfort symptom, which stays in the template as context. The other 13 days -- five fault-free days and eight airflow-bias days, which neither rule targets -- are the negatives. On the full subset (31 days, camber datasets score ornl-frp-vav on a --subset full ingest, or scripts/catalog_sweep.py --only ornl-frp-vav):

Detector Positives caught (TPR, 95% Wilson CI) False alarms (FPR, 95% Wilson CI)
actuator_stuck → stuck box damper (declared since 0.98) 17 of 18 — 94% [74–99%] 0 of 13 — 0% [0–23%]
unmet_setpoint_hours → stuck box damper (declared until 0.97) 10 of 18 — 56% [34–75%] 1 of 13 — 8% [1–33%]

The default subset (set 3 only): actuator_stuck 6 of 6, 0 of 1 (TPR 100% [61–100%]); unmet_setpoint_hours 2 of 6, 1 of 1.

By room, actuator_stuck: 104 caught 6 of 6, 205 caught 6 of 6, 106 caught 5 of 6. It misses room 106 stuck at 100 % (set 1): the room ran warm that day, so a fully open damper was what the room asked for, and a box stuck where the load would have put it anyway cannot be told from a working one. Seven of the 17 detections are warnings: the days (room 205 at 60 / 80 %, room 104 at 60 / 100 %, room 106 at 40 / 60 / 80 %) where nothing in the room contradicted the position. The nine neighbouring boxes are not scored; on the 31 days one neighbour is flagged, room 205 in set 1 at 80 %, fully open while its room sat below setpoint on a duct-static-collapse day, when the air handler starved every box (data issue duct-static-collapse-in-damper-runs).

By room, unmet_setpoint_hours: 104 caught 5 of 6 (misses 60 %), 106 caught 3 of 6 (misses 40 / 60 / 80 %), 205 caught 2 of 6 (20 % and 40 %; misses 0 / 60 / 80 / 100 %). Its one false alarm is room 205's set-3 fault-free day (2023-12-14): the room overheated in the afternoon from solar gain through its south and west windows (too hot 22 % of occupied hours), which the data descriptor's technical validation reports -- real weather, not a fault.

Caveats, stated because the intervals are wide:

  • Calibrated on the same building. actuator_stuck's min_flat_hours and whole_day_share defaults were set from the set-3 boxes, which are also scored here: the healthy boxes' longest flat run covers at most 70 % of a day there, and at most 95 % on the full subset (room 102 on an airflow-test day), against 100 % for every stuck box. The 0.98 whole-day bar sits in that narrow gap, so the result is not an independent test.
  • A symptom rule is not a damper detector. A damper stuck near the flow the room needs that day leaves no comfort symptom, so unmet_setpoint_hours misses mid-range positions; whether a stuck position is caught depends on the day's weather and load as much as on the fault.
  • Small n, one building, one day per case. 18 positives in three rooms and 13 negatives; the per-room splits are anecdote, not rates.
  • Not a CI-gated benchmark and not in the dossier (camber validate): the number comes from the catalog data, and is published here so it can be reproduced and re-checked.
  • Nothing else is scored on it. The airflow-bias days are emulated by moving the box's minimum airflow setpoint (the logged flow is true -- data issue airflow-bias-emulated-by-setpoint), and no CAMBER rule targets them; the rogue-zone and cohort-starvation censuses run per test day as context. A cohort comparison does not replace the per-box rule: grouped per day, neither the raw mean airflow nor the share of each box's peak airflow isolates the stuck box (camber.rules.cohort).

Fan-powered box fan heat by box type (lbnl-fpu, 0.100)

reheat_penalty(fan_heat_f="auto") learns a box's closed-valve lift over the entering primary air. Over the occupied, airflow-bearing hours with the valve shut, the median lift on the fault-free runs is 0.0 °F on the parallel box (its fan runs in heating only) and 13.7 °F on the series box (its fan always runs and pulls in plenum air). Until 0.100 the estimate was clipped at 8 °F for every box. box_type="series" caps the open-valve (no-rise) allowance at 10 °F and keeps the closed-valve (big-rise) allowance at 8 °F. All 62 runs were read hourly, through the measured position and through the demand alone. Every verdict (severity and consistency) is the same as with the 8 °F clip. On the SFPU runs, the stuck valves' full-demand rise is at most 12.9 °F (stuck at 20 %), against the old 13 °F bound and the new 15 °F bound. The working full-valve rise is at least 17.6 °F. A symmetric higher cap does harm: at 9-11 °F the big-rise check loses the passing-valve caveat on the 50 % and 80 % leaks and on the valves stuck at 80 % and 100 % (demand only), because the lift is learned from the same closed-valve samples the check judges. box_type="parallel" matches the default on every PFPU run. The caps were chosen on these labelled runs, so this is an in-sample check, not a rate. The drift.vav_* and drift.sfpu.* opt-in numbers come from vav_reheat_valve_drift, not this rule, and are unchanged.

0.93 air-side checks on real, unlabelled data (setback, leaking valve, reheat capacity)

Three rules changed or added in 0.93 were checked on the open catalog data that showed the problem. None of these sets labels the fault, so these are before/after readings, not rates.

night_weekend_setback on ornl-frp-ops (#43). The catalog template (occupied 07-22 every day, the tests' own schedule, with the descriptor's 15.6 / 29.4 °C unoccupied setpoints) at 1-minute resolution:

Test Unoccupied fan runtime 0.92 verdict 0.93 verdict
Heating baseline (24/7 by design) 100 % MISSING MISSING
Heating setback 56 % MISSING effective (fan cycling to hold): 71 % duty in the night hours it runs, return air 63.0 °F vs 67.3 °F occupied, against a 60.1 °F setback
Pre-heat (on 10:00-05:00 by design) 100 % MISSING MISSING
Cooling baseline (24/7) 100 % MISSING MISSING
Cooling setback 6.3 % effective effective
Free float, heating and cooling 0 % effective (floor) effective (floor)

The verdicts are the same at 1-minute, 15-minute and hourly resampling. The RTU has no zone temperature, so the return air read while the fan runs stands in for the zones (the finding says so). ornl-frp-vav's rooftop units, whose fans are off at night, are unchanged.

leaking_valve on irish-ahu and lbnl-sdahu (#42). On the Irish AHU the supply-air check read a heating-leak signature in 34 % of both-valves-closed hours before the documented 2022-05-01 valve replacement (fault) and 0.2 % after. Most of that sits downstream of the coils: the supply air reads 2.6 °F above the cooling coil's leaving air in the median closed hour before the date and -0.7 °F after. With the coils' own leaving-air temperatures mapped, the heating coil rises more than 3 °F above the mixed air in 11 % of closed hours before the replacement (warn; mostly the cold 2020/21 100 %-outdoor-air winter) and 0 % after (ok); the whole record reads ok. On the LBNL single-duct AHU the scored runs keep their verdicts (fault-free and the damper runs quiet), and with the default parameters the one leak run (coi_leakage_010) is still missed: with the fan running and the valve commanded shut, its supply air sits a median 0.1 °F below the mixed air against +1.0 °F on the fault-free run. That is a 1 °F shift, well inside the 3 °F threshold.

leaking_valve with a measured fan heat on lbnl-sdahu (0.98, #84). The default cooling-leak test credits no fan heat, so a leak that only cancels the fan's rise goes unseen. The lbnl-sdahu template now sets measured_fan_heat_f: 1.0 (the fault-free run's median supply-minus-mixed rise, 1.06 °F over 1,400 occupied, fan-on, valve-shut hours), cool_delta_thr_f: 1.0 (a leak takes the supply air below the mixed air) and occupied_only: true (unoccupied fan cycling put 24.2 % of the fault-free run's valve-shut hours below that line, against 2.4 % occupied). Hourly, the leak run reads 60.5 % of its valve-shut hours below the line (fault, was ok), the fault-free run 2.4 % and the damper runs under 2 % (ok). The LBNL benchmark reads the same template, so SDAHU overall TPR moves 40 % → 60 % (accuracy 50 % → 67 %) and the pooled TPR 70 % → 80 % (accuracy 77 % → 85 %), with FPR still 0 %.

Circularity. The 1.0 °F was calibrated on AHU__fault_free, and that run is also a scored negative in camber datasets score and the benchmark, so its clean verdict here is in-sample, not a held-out result. A half-year split is the honest check: calibrated on January-June (median 1.0 °F) and judged on July-December, the fault-free run reads 2.4 % (ok) and the leak 54.3 % (fault); calibrated on July-December (1.1 °F) and judged on January-June, 2.7 % (ok) and 77.2 % (fault). Both halves are the same simulated unit, so this shows the value is stable over the year, not that it transfers to another building: measure your own unit's fan heat (TUNING.md). On the dual-duct unit the rule is not run: its mapped supply air is the cold deck, which the hot-deck heating coil never touches (judge_heating_on_supply_air: false leaves that coil unjudged).

A leak judged against the unit's own baseline: coil_leak_drift (0.100, #100; opt-in). The calibrated fan heat above is circular. The drift detector avoids calibrating anything: it fits the coil's valve-shut rise (supply or coil leaving air minus mixed air, fan-on hours with every coil valve shut) against the mixed air on a known-good window, then flags a shift in the current window at the same mixed-air temperature. A cooling leak moves the rise down, a heating leak moves it up. Only current hours inside the baseline's mixed-air range are judged. It is opt-in: an ahu drift family entry names "coil_leak": ["cooling"] (see the CLI guide). examples/lbnl_fdd/leak_drift.py scores it on both LBNL units with labelled leaks. The dual-duct archive has no leak run. These are measured, not gated results, and nothing here was fitted on a scored run. The script scores each run three ways:

  • split (the benchmark's drift design): the baseline is the fault-free run's first 60 %;
  • twin (a declared reference equipment): the baseline is the whole fault-free run, which is not itself scored;
  • onset (a declared known-good period): each run is spliced onto the fault-free run at 2018-07-01, and the healthy half is the baseline. The fault-free run spliced onto itself is the seasonal negative.
Unit (runs) Mode TPR (95 % CI) FPR (95 % CI) Notes
SDAHU (one 10 % cooling leak; fault-free, 4 stuck dampers) split 1/1 (0.21-1.00) 0/3 (0.00-0.56) leak −1.10 °F (−3.7σ) over 1,384 hours; fault-free tail +0.03 °F. Dampers stuck at 10 / 25 % decline: they have no fan-on hour with the valve shut
twin 1/1 (0.21-1.00) 0/2 (0.00-0.66) leak −1.11 °F (−3.6σ)
onset 1/1 (0.21-1.00) 0/3 (0.00-0.56) leak −1.05 °F (−3.5σ); the fault-free second half +0.02 °F
FCU (cooling and heating leaks at 20 / 50 / 80 %; 33 negative runs) split 6/6 (0.61-1.00) 1/33 (0.01-0.15) leaks −14 to −19 °F (cooling) and +26 to +39 °F (heating), each on the right coil. The false alarm is the room-sensor bias −4 °C (+4.9 °F, +2.5σ, on 104 hours; 234 more fell outside the baseline's range)
twin 6/6 (0.61-1.00) 0/32 (0.00-0.11)
onset 5/5 (0.57-1.00) 0/33 (0.00-0.10) heating leak 50 % declines: fewer than 10 valve-shut hours after the onset

The FCU negatives are the fault-free run and the damper, fouling, filter, fan-outlet, OA-inlet, room-sensor and unstable-control faults. Valves stuck closed are negatives too.

Two groups are reported and not scored:

  • Same symptom. A valve stuck partly or fully open, or a reversed valve signal, passes water while it is commanded shut, which is physically the same symptom. The detector fires on all four SDAHU stuck-valve runs (−1.1 to −17.4 °F) and on 9/10 FCU runs. The FCU heating valve stuck at 20 % reads +3.4 °F (1.7σ).
  • Confound. A supply-air sensor bias moves the supply-minus-mixed rise exactly as a leak does. The SDAHU coi_bias_-2 / -4 runs fire as cooling leaks (−4.6 / −8.2 °F). The positive biases move the rise up, which a cooling-only unit does not judge. Every finding carries the "check both sensors against a reference thermometer" caveat for this reason. A coil leaving-air sensor narrows the confound to that one sensor.

Before / after. The default outputs do not change: the detector runs only when a config opts in. Compared with the point-in-time leaking_valve on the same whole-year runs:

Unit leaking_valve coil_leak_drift (split)
SDAHU defaults: misses the leak (TPR 0/1, FPR 0/3); lbnl-sdahu template: catches it (1/1, 0/3), but its fan heat was calibrated on a scored run catches it (1/1, 0/3), with no calibration
FCU defaults: TPR 6/6, FPR 24/33 (0.56-0.85). Healthy runs show a heating-leak signature in 10-20 % of valve-shut hours TPR 6/6, FPR 1/33

Through camber drift run on the lbnl-sdahu store, with AHU__fault_free as the declared reference and coil_leak: ["cooling"], the leak reads warn at −1.11 °F (−3.6σ), the same as the script's twin mode, and the AHU roll-up puts it on the coil side.

Sensitivity. The defaults (warn_sigma 2.5 and fault_sigma 4.0, from coil_valve_drift; warn_f 0.5 °F; occupied_only off, as in leaking_valve) were not fitted to these runs. With warn_sigma anywhere from 2.0 to 3.0 every leak is still caught, and the FCU false alarms range from 2/33 to 0/33. Above about 3.4σ the SDAHU leak is missed. With occupied_only on, the SDAHU results do not change, but the FCU false alarms rise to 3-4 of 32-33: the stuck-80 % damper and the ±4 °C room-sensor biases.

What is thin. SDAHU has a single leak run (its four published "severities" are one file), so its TPR interval spans 0.21-1.00. The FCU leaks are large, and the point-in-time rule also catches them. The small leak that the drift detector exists for appears once in the open data.

Not gated (maintainer decision, 0.100). The gated keys that were proposed, drift.coil_leak_drift.recall 1.0, .precision 1.0, .f1 1.0 and .fpr 0.0 from the benchmark's SDAHU drift section, were declined. The results above are measured, opt-in records, re-run with examples/lbnl_fdd/leak_drift.py. No benchmark baseline carries a coil_leak_drift key, and the LBNL benchmark does not run the detector.

reheat_capacity_shortfall on lbnl-b59 (#44). Of the 35 underfloor terminals with a heating setpoint and a reheat valve, zone 051 (RTU01) sits more than 1.5 °F below its 72 °F setpoint with its valve at 90 % or more in 35.8 % of occupied hours (1,586 h over three years, median 2.9 °F below): a fault. Nine more read warn at 5-18 %, and 25 read ok. On ornl-frp-vav the rule declines: its electric reheat is logged as energy, not as a valve or command.

Multi-zone fleet + reset validation (generated — camber.fleetlab)

The rogue-zone census, cohort-starvation, and reset-effectiveness detectors need something no vendorable public dataset provides — a fleet of zones with per-zone reset requests and a served-by topology. So camber.fleetlab generates it from the public ASHRAE Guideline 36 Trim-&-Respond logic itself (§5.1.14 / §5.14.8), never copying any encumbered simulation. The fleet is physically coherent: each zone's per-cycle requests come from the same G36 request rules the detectors consume, are aggregated per air handler, and the healthy reset setpoint is literally g36_reset.tr_simulate of that aggregate — so the reset a detector scores is the true T&R response to the fleet's own demand. One fault is then injected per fleet (a rogue zone, a starved cohort, or an inert reset in one of four G36 failure modes), and examples/fleet_fdd/benchmark.py scores all six detectors (3 detectors × SAT + static) with camber.eval.benchmark, CI-gated at tol 0.0.

flowchart LR
    gen["generate_fleet<br/>(G36 Trim-&-Respond)"] --> zf["per-zone frames<br/>+ topology + labels"]
    zf --> census["rogue_zone_census<br/>cohort_starvation"]
    zf --> reset["reset_effectiveness<br/>(fleet-derived requests)"]
    census --> ev["eval.benchmark<br/>TPR / FPR + attribution"]
    reset --> ev
    ev --> gate["check_against_baseline<br/>(CI gate, tol 0.0)"]

Crucially the score is more than a fire/no-fire bit: an attribution rate checks each detector named the right zone (worst_zone), the right air handler (worst_group), or the right reset failure mode (reason) — the guard against a generator so easy that firing is meaningless — and each detector carries genuine negatives (the fault-free fleet plus the cross-archetypes: a rogue fleet is a cohort/​reset negative and vice-versa) so FPR is actually measured, not assumed. This is internal-validity accuracy (does the detector correctly identify the G36 pattern it claims to); external validity rests on the citation of the public G36 standard, not on real data — stated plainly because no real labeled fleet is vendorable.

Future external validity. The open Modelica Buildings Library G36 sequences (revised BSD-3 — license-clean) could cross-check the generated reset-request signal, but executing them needs a Modelica toolchain (OpenModelica/Dymola) outside this project's dependency-light envelope, so it is deferred; the generator instead cites the G36 standard directly.

FDD accuracy — synthetic whole-suite harness

LBNL's public data labels only a handful of AHU fault modes, so it can accuracy-score only a few detectors. To measure the rest of the suite, camber.faultlab injects each rule's target fault into a role-frame (a labeled positive) and a matching fault-free frame (a negative), and examples/synthetic_fdd/benchmark.py scores the whole registry with the same camber.eval framework — deterministically, with no download, gated in CI against a committed baseline (tests/test_faultlab.py).

Current coverage (0.98): all 46 single-equipment rules are accuracy-scored (100% TPR / 0% FPR on their injected faults) — the fixture-only list is empty; the fleet rules are scored separately. A companion harness scores the G36 FC1–FC15 engine over 6 representative fault conditions. The runner prints a scored-vs-fixture coverage table so the credibility story is explicit rather than implied. This complements — does not replace — the real-data LBNL benchmark above (external validity on real equipment), which 0.6 set out to broaden with a cooling-coil-valve leakage severity sweep. That sweep does not exist: the published SDAHU zip's coi_leakage_010/025/040/050 files are byte-identical (one simulation under four labels) and there is no 100 % file, so the benchmark scores the single leak run once — as coi_leakage_010, the label that matches the data (a 10 % leak). (The four oa_bias_* files are likewise one run, and carry no OA-temperature bias at all; the FCU set's cooling / heating "airside minor fouling" files are identical.)

Baseline refresh, 0.91 (maintainer sign-off). The committed synthetic baseline (examples/synthetic_fdd/benchmark-baseline.json) was refreshed once for 0.91, to add the two rules that release registers, each with a faultlab scenario: g36_afdd (the G36 engine as a rule; the scenario is FC13, supply air 10 °F over setpoint in full cooling) and chw_supply_tracking (a plant supplying 48 °F against a 40 °F setpoint while its chiller runs). New keys: g36_afdd.tpr 1.0, g36_afdd.fpr 0.0, chw_supply_tracking.tpr 1.0, chw_supply_tracking.fpr 0.0; coverage.n_scored and coverage.n_single went from 36 to 38. Every other synthetic key is byte-identical to 0.90.1 (the G36 engine harness keys g36.* included), and the fleet, LBNL, BDG2 and BDG2 savings baselines did not move.

Baseline refresh, 0.92 (maintainer sign-off). Refreshed once more for 0.92, to add the condenser-water tower-bypass leak rule (#15), whose faultlab scenario (condenser_bypass_leak: a running plant with the bypass commanded shut and 60% of the condenser return mixed back in) was held in faultlab.PENDING_SCENARIOS until the sign-off and is now in SCENARIOS. New keys: condenser_bypass_leak.tpr 1.0 and condenser_bypass_leak.fpr 0.0; coverage.n_scored and coverage.n_single went from 38 to 39. Every other synthetic key is byte-identical to 0.91.0, and the fleet, LBNL, BDG2 and BDG2 savings baselines did not move.

Baseline refresh, 0.93 (maintainer sign-off). Refreshed for 0.93 to add the six new single-equipment rules, whose faultlab scenarios were held in faultlab.PENDING_SCENARIOS (now empty) until the sign-off and are now in SCENARIOS: reheat_capacity_shortfall (#44: a VAV box with its reheat pinned at 100 % and the zone 3 °F below its 70 °F setpoint), and from #40 dx_refrigerant_charge (a running split system with 0.8 °F of liquid subcooling), dx_indoor_airflow (a 32 °F evaporator split), hp_mode_vs_need (a water-to-air heat pump cooling a 64 °F room every morning), hp_capacity_shortfall (heating all occupied day with the room still at 64 °F) and source_loop_deltat (a ground loop pumped around the clock with ~0.2 °F across it). New keys: each rule's .tpr 1.0 and .fpr 0.0 (12 keys); coverage.n_scored and coverage.n_single went from 39 to 45. The other new 0.93 rules are not single-equipment rules with a scenario: co2_ventilation_system and hp_room_imbalance are fleet rules and discharge_superheat_drift is a drift detector. Every other synthetic key is byte-identical to the 0.92 baseline, and the fleet, LBNL, BDG2 and BDG2 savings baselines did not move. The harness's cross-fire diagnostic (reported, not gated) shows three co-detections on the new faulty frames: unmet_setpoint_hours on the reheat scenario (the zone is below its setpoint), supply_air_reset on the DX-airflow one (44 °F supply air) and hp_capacity_shortfall on the heat-pump mode one (it calls the cold room with the unit cooling a control problem, which is what it is).

M&V accuracy — real-data acceptance on BDG2

The M&V analogue of the LBNL FDD accuracy benchmark: examples/bdg2/benchmark.py scores the ASHRAE Guideline 14 baseline-model acceptance rate on real whole-building meters (Building Data Genome 2, CC-BY-SA 4.0, ~2,000 meters). For each building it fits the daily change-point inverse model of energy vs outdoor temperature and asks whether the fit meets the G14 gate (CV(RMSE) ≤ 30% daily); the headline is the fraction that pass, with a Wilson CI. Committed baseline, gated in the benchmark CI job.

Representative result (2016 cleaned meters, whole days only, ~2,011 buildings):

Meter Acceptance (95% CI) Median CV(RMSE) n
Chilled water (cooling) 36% [32–41%] 31% 514
Electricity 10% [8–11%] 17% 1,497
Pooled 17% [15–18%] 20% 2,011

The honest read: weather-driven chilled-water energy is baseline-able at a meaningfully higher rate than schedule/plug-driven electricity (~3.7×) — CAMBER reproduces the expected physics — but real whole-building energy is messy, and half the chilled-water buildings sit near the 30% daily CV(RMSE) line. Reporting both meter types (not just the flattering one) with confidence intervals is the point. The runner also rolls the portfolio up by EUI at real scale (validating the fleet percentile path on a real distribution).

M&V savings — placebo and injection on BDG2

The acceptance benchmark above asks whether a baseline fits. examples/bdg2/savings_benchmark.py asks whether the savings and their bands hold up on the same real meters (issue #21 phase 21e). The baseline year is 2016 and the reporting year 2017. It uses the publisher's cleaned meters and whole days only, as above, and a meter enters when it has at least 328 whole days in each year: at most 37 of 365 missing, the CalTRACK 2.0 §2.2.1.2 data-sufficiency rule. A meter that reads one constant value all year (a dead meter) is left out. The data are fetched, never redistributed, and every random draw is seeded.

It runs four experiments:

  1. Placebo. Nothing is injected, and no building is known to have had a measure, so every saving is error. The benchmark uses the two metrics of Touzani, Granderson, Jump & Rebello, Energy & Buildings 193:216–225 (2019):
  2. the error-uncertainty ratio EUR = (actual − predicted) / band (their Eq 15);
  3. the uncertainty-interval coverage factor UICF, the share of buildings with |EUR| ≤ 1 (their Eq 16).

It scores forecast and backcast with both kernels (G14 and exact) and standard conditions with the exact kernel, at nominal 90%. It also scores the G14 forecast at 95%, for comparison with Touzani et al., who found about 71% for G14 at 95% on daily linear models of 69 buildings chosen to have no anomalous changes. Under-coverage is expected. A band carries model error only, and a real building's year-to-year change lies outside it, so the gate is on regression against the committed baseline, never on the nominal rate. 2. Injected savings of 5, 10 and 20%. Every reporting-year reading is multiplied by 1 − s, so the true SEnPI is 1 − s on every basis. For each method the benchmark reports: - the error of savings_pct against s (median and 90th percentile of its absolute value, and its signed median); - how often the SEnPI band covers 1 − s; - how often the band lies wholly below 1, a saving it can tell from none.

Forecast recovery is exact by construction (its error is the placebo error), so it is asserted as an identity rather than measured. Backcast and standard conditions are the methods under test. Standard conditions uses a two-year day-of-year normal of the site's own temperatures. 3. Injected steps. The benchmark plants one step (10% or 20% of the meter's mean daily energy) or two steps (20% each), with random sign and date, in the reporting year. It scores: - detect_step_changes: the share of planted steps found within 7 days, the date error, and detections that are neither planted nor present in the un-injected series; - the indicator NRA fitted at the true date (estimate_nre_indicator): its recovery of the planted effect δ, and whether its 90% interval covers δ; - whether the detector's own step band covers δ.

The real series keeps its own level shifts; they are part of the noise the detector must work through. 4. Injected static-factor change. A floor-area ratio r = 1.25 affects a stated share f = 0.6 of the load, from the start of the reporting year or from 1 July. The benchmark scores the proportional StaticFactorAdjustment's recovery of the placebo saving, and how often the band covers the true zero saving with and without the adjustment.

Sampling. Placebo and injected savings run on every eligible meter. Steps and static factors run on a deterministic subsample of 150 meters per type (--sample), drawn with a fixed seed from the sorted eligible list. Each building's draws use a seed derived from its id, so they do not depend on which other buildings were sampled or on how many worker processes ran (--jobs).

The gate. The gated metrics live in their own file, examples/bdg2/savings-benchmark-baseline.json. benchmark-baseline.json and its keys are untouched, and the benchmark CI job gates each file separately at --tol 0.05. A regression is a fall in coverage, detection or significance rates, or a rise in an error, |EUR| quantile, spurious-detection or decline rate. Signed quantities (the median EUR, the median savings bias) are written under info. keys and are not gated, since neither direction is better. camber validate carries the placebo UICF of the forecast kernels as the cited track bdg2_mv_savings, and tests/test_dossier.py checks it exactly against the committed baseline.

Representative result (2016 baseline, 2017 reporting; 1,023 electricity and 334 chilled-water meters). With nothing injected, the nominal-90% forecast band covers zero for 33% of electricity and 52% of chilled-water meters (G14 kernel; exact kernel 36% / 54%). At nominal 95% the G14 figures are 38% / 57%, against the ~71% Touzani et al. found on 69 buildings screened for anomalous changes (Touzani, Granderson, Jump & Rebello, Energy & Buildings 193:216–225, 2019). BDG2 is not screened: a real building's year-to-year change lies outside a band that carries model error only. An injected 10% saving is recovered with a median absolute error of about 5 points (electricity) and 7 points (chilled water) by every method; the band tells it from zero in 82–84% / 68–75% of meters. detect_step_changes finds 47% of planted 20% steps on electricity (39% on chilled water) with a median date error of 0 days, and 0.27 / 0.33 spurious detections per series. The proportional static-factor adjustment restores the placebo saving exactly for a change at the start of the period, and to a median error of 0.2 points (electricity) and 0.3 points (chilled water) for a mid-year change.

Every G14 figure above carries the kernel's caveat: in simulation, with a correct model, the G14 band under-covers (about 82–88% at nominal 90%) while kernel="exact" is on target (next section; MANDV). tests/test_dossier.py checks each percentage in this paragraph against the committed baseline.

Monte Carlo coverage of every kernel

tests/test_mandv_mc_coverage.py is the index. For every savings path it names the seeded Monte Carlo that checks the band: synthetic daily 3PC data with AR(1) residuals at ρ ∈ {0, 0.4, 0.8}, ρ estimated from the fit, and a known true saving. Cells tested elsewhere are referenced rather than repeated, and a registry test fails if a referenced test disappears: - forecast, exact kernel; - the SEP chain; - the indicator NRA band; - the adjusted forecast and the adjusted SEP chain; - the step detector.

The new cells are: - forecast and backcast with the G14 kernel; - backcast and standard conditions with the exact kernel; - standard conditions with the G14 kernel; - the sequential chain; - a proportional static factor on a forecast (both kernels); - a backcast adjusted for a reporting-period indicator.

The gates: - every exact-kernel cell at [0.85, 0.95]; - the G14 cells at [0.78, 0.95], because the G14 kernel falls short of nominal on a year of daily data even when the model is right; - the conservative constructions (G14 standard conditions, the sequential chain's independence sum) at a floor.

An adjusted backcast whose reporting period holds an indicator NRA refits the reporting model with the indicator (joint Σ, p + 1). Its exact band covers 86% / 88% / 86% at ρ = 0 / 0.4 / 0.8 (600 runs each), unbiased, and is gated at [0.85, 0.95]. Before that change the band was the reporting model's fitted through the event, about 20× too wide; that band survives, with a caveat, only where nothing can be refitted, and a test pins it at a floor.

M&V savings — SEP chaining on real meters (valladolid-uva)

The published real-data chaining case (issue #50). The case planned in 0.90, lbnl-b59 2018→2019→2020, is not publishable: its meters need a column remap, dropout fills and a metering-boundary annotation before any saving means anything (see DATASETS.md), so it stays a data-issues teaching case with no published savings. examples/valladolid/chaining.py runs the chain on two buildings of the University of Valladolid instead (Mendeley Data doi:10.17632/mzkyh37mtr.2; buildings described in Mariano-Hernández et al., Energy Science & Engineering 10:4694–4707, 2022, doi:10.1002/ese3.1298). Building 1 (file A) is stable across the years and is the control. Building 2 (file B) had equipment replaced and on-site renewable generation added, which its meter nets out, so a saving measured on it includes that generation.

The analysis is declared in the script before any saving is read: - stamps moved from the end to the start of each hour, whole days only; - working days only (the publisher's academic calendar, 2016–2019), one row per month, weighted by its working days (the 0.92 days-weighted fits); - hourly OAT from CAMBER's weather source (the nearest ISD station with the NASA POWER and Open-Meteo fallbacks), with the file's daily NASA POWER temperature as a sensitivity; - baseline 2016, reporting 2019, calendar-year intermediates 2017 and 2018, plus select_method's own proposal; 2020 (the COVID-19 closure) is outside every period.

Result (2016 baseline, 2019 reporting, working days, 90% bands). Every yearly model of Building 1 is SEP-valid and passes G14 (4P, R² 0.91–0.95, CV(RMSE) 4.3–6.2%, 10–11 monthly rows of 177–188 working days). Building 2's are SEP-valid in every year but pass G14 only in 2018 and 2019 (3PH, R² 0.88 / 0.83; 2016 and 2017 reach R² 0.66 / 0.64). The chain through the 2018 intermediate, whose model is valid under both SEP and G14 for both buildings, gives: - Building 2: SEnPI 0.838 ± 0.037, a 16.2% saving (76,500 kWh of 2019 working-day electricity). The saving includes the on-site generation behind the meter; the data cannot separate it from the equipment replacement. - Building 1 (the control): SEnPI 1.022 ± 0.046, no change distinguishable from zero.

Through the 2017 intermediate the chains agree (0.836 ± 0.077 and 1.001 ± 0.050); Building 2's band is wider because its 2017 model is the weaker one. select_method proposes forecast for both buildings, the first valid method in SEP's order. Its three valid methods agree on Building 2 (SEnPI 0.838–0.839) but spread on Building 1: forecast 1.066 ± 0.036, backcast 1.049 ± 0.049, chaining 1.024 ± 0.046. This is the spread between valid methods that Chen & Therkelsen (2019) describe, and the reason the proposal carries no headline figure. With the file's NASA POWER daily temperature in place of the station series, Building 2's 2018 chain reads 0.829 ± 0.040 and Building 1's 1.002 ± 0.049. Building 1's forecast moves from 1.066 to 1.028, so on that building the forecast depends on the weather source and the chain does not.

Point-role suggestion: real point names, anonymised names, synthetic names

The scripts are in examples/suggester_eval/. None of these figures is a gated benchmark.

Real BMS point names (real_names.py). Every mapped point of seven open real-building catalog datasets is scored by its published name:

  • lbnl-b59 (Luo et al. 2022)
  • irish-ahu (Ahern et al. 2023)
  • nuig-ahu101 (Messervey et al. 2019)
  • robod (Tekler et al. 2022)
  • b4b-windesheim (ter Hofte et al. 2023)
  • sdu-ou44 (Schwee et al. 2019)
  • ornl-frp-ops (Yoon et al. 2022)

The labels are each dataset's catalog mapping, hand-curated by CAMBER. The name tokenizer was written against the irish-ahu names and partly the lbnl-b59 ones, so those two are in-sample for the name.

real buildings points name only top-1 / top-3 % data only top-1 / top-3 % name + data top-1 / top-3 %
pooled, all seven 422 82.5 / 82.9 38.9 / 54.7 83.9 / 89.1
pooled, excluding the in-sample two 129 52.7 / 53.5 43.4 / 58.9 58.1 / 72.9
LBNL simulated FDD sets (reported apart) 72 48.6 / 58.3 23.6 / 37.5 56.9 / 66.7

On real names, adding the data changed the top-1 result of 16 points: it helped 11 (room temperatures whose names read as outdoor, unreadable VAV discharge temperatures) and hurt 5 (weather-station outdoor temperature and humidity, one heating valve).

BTS, anonymised names (bts.py; Prabowo et al., NeurIPS 2024 Datasets and Benchmarks, doi:10.48550/arXiv.2406.08990; three Australian buildings, 903 points, leave one building out). The rows marked Brick-class labels used as names are an upper bound, not real-world naming: BTS publishes no point names, and the Brick class text is effectively the label.

method names top-1 % top-3 %
name only (0.95 default) anonymised 0.0 0.0
data only, role templates anonymised 48.0 65.2
data only, fitted on the other two buildings anonymised 38.4 58.8
name only (0.95 default) Brick-class labels used as names (upper bound, not real-world naming) 93.0 97.2
name + data (use_timeseries=True) Brick-class labels used as names (upper bound, not real-world naming) 95.2 99.9

The template rows are optimistic, because the templates were adjusted while looking at these results. The fitted rows are the out-of-sample reference.

Synthetic vendor-style names (messy_names.py). A seeded generator names the BTS points in five styles, from AHU1_SAT to ahu_03_supply_temp. The name alone places 25-88 % first, and the name with the data places 52-91 % first. These figures are synthetic and are never pooled with the real ones.

Per-dataset tables, confusions, leakage notes and attribution: MAPPING-ASSIST.md.

Cross-validation vs an independent implementation

The ASHRAE G36 fault-condition equations (FC1–FC15) are cross-validated against the open-source open-fdd project as of its 0.1.5 release — they agree to 0.00 pts on every shared, runnable fault condition (one ≤2.3-pt mixed-air-bounds edge case). Current open-fdd is a different engine. It was re-compared in 2026-09 (PyPI 4.4.9 and the SQL engine fdd_cli, both from commit 32a6d44): each engine at its own defaults and at G36 tolerances, on the labelled LBNL AHU runs, with per-engine detection rates and Wilson intervals. The harness is examples/openfdd_crosscheck. The results, the FCs not evaluated and why, the causes of the differences, and where the 0.1.5 result no longer applies are in ECOSYSTEM.md.

M&V

Change-point / TOWT models report ASHRAE Guideline 14 fit statistics (CV(RMSE), NMBE) and fractional savings uncertainty with every saving. (True of TOWT only since 0.81.0 — before that no code path could produce an FSU from a TOWT model at all, because its predict takes an index as well as temperatures and every savings consumer passes one array.) The CalTRACK alignment and an eemeter cross-check recipe (no dependency added) are documented in MANDV.md.

The FSU kernel was wrong until 0.80.0 and is now checked two ways. The bracket had n′ where the published form has n/n′, which made every band a factor of √n too wide — 19× for a year of daily data — and made the autocorrelation correction move it the wrong way. The corrected form was verified against Reddy & Claridge (2000) as reproduced in the public BPA/LBNL/NYSERDA M&V guides (the ASHRAE text is paywalled and was not consulted, consistent with the clean-room rule), and independently against a Monte Carlo of AR(1)-residual fits. Honesty runs in both directions here: a 19× band overstates nothing, but it makes a defensible saving look unusable, and the ρ hook understated. The examples/bdg2 harness now also reports the measured lag-1 residual autocorrelation across real meters, so the correction rests on CAMBER's own number rather than a literature range.

Extrapolation is checked, not assumed (issue #20). Until this release no savings path asked whether the reporting period's drivers lay inside the range the baseline was fitted on, so a spring baseline projected onto a summer reported a saving and a band as if the model held there. Every savings path now grades coverage (mandv.coverage): in-range results are byte-identical to before (a golden test freezes them from the prior release), moderate extrapolation is disclosed and widens the band, and severe extrapolation is declined by default. The BDG2 benchmark above fits and scores each baseline in sample, so its numbers do not move; an out-of-sample extrapolation sub-benchmark is follow-up work. The tiers and thresholds are CAMBER policy choices, documented in MANDV.md.

Tariffs & finance

The native tariff engine is cross-checkable against NREL PySAM UtilityRate5 (the optional [tariff] extra) for full URDB fidelity, and validate_bill reconciles a recomputed bill against actual invoices. The ECM finance metrics (NPV/IRR/SIR) are the textbook definitions; IRR is a bisection solver verified against hand-worked cases in tests/test_finance.py.

Uncertainty & reproducibility toolkit (camber.validation)

  • wilson_interval(k, n) / rate_ci — binomial confidence intervals for any rate.
  • metrics_with_ci(confusion) — TPR/FPR/accuracy each with a Wilson CI.
  • check_determinism(fn, ...) — reproducibility guard (identical output across runs).

Robustness / adversarial hardening (pre-1.0)

A dependency-light stress pass (seeded generators + parametrize, no hypothesis) exercises the core entry points on degenerate/adversarial input, and each real bug it found is fixed and regression-locked:

  • io.load_csv — empty / header-only / unparseable-timestamp / text-in-numeric CSVs now raise a clear error or coerce cleanly (a stray text cell no longer silently poisons a column to object).
  • Every registered rule on empty / 1-row / all-NaN / all-equal / duplicate-index frames returns a Finding and never raises (a 191-case parametrized sweep) — two plant rules were hardened.
  • M&V calibration degrades to accept=False (never a ValueError) on thin/degenerate energy.
  • Fleet rollup percentile is O(N log N) (was O(N²)); scale-tested to N=500.
  • Mapping rejects catastrophic-backtracking (ReDoS) regex patterns at config load.
  • Determinism sweep — check_determinism now nets calibrate / best_model / detect_level_shifts / cohort / faultlab, not just two spots.
  • Analytics entry points (0.9.6) — forecast / disaggregate / tariff reject a non-timestamp index up front (they used to coerce a numeric index into nanosecond dates and return a plausible wrong answer); EnergyPrice rejects a negative/NaN rate; build_scorecard rejects None. Empty input stays graceful (empty in → empty out).
  • Untrusted parsers (0.9.6) — the hand-rolled Brick reader and the rdflib/Haystack/223P paths now degrade on malformed input to a clear ValueError (or a partial result), never a raw IndexError / rdflib BadSyntax / AssertionError: a triple missing its terminator, a predicate list with no object, a literal containing the split characters, and a malformed tag set are all fuzzed and locked.
  • Tariff billing (0.9.6) — a malformed rate structure (empty energy_rates, or a schedule naming a period with no rate) raises a clear error naming the period, instead of an IndexError mid-bill.

Continuous benchmarking in CI

Accuracy is gated against a committed baseline so it can't silently drift. The cross-equipment runner emits a flat metrics dict and compares it to a baseline:

# seed a baseline once (after a known-good run), commit it:
python examples/lbnl_fdd/benchmark.py --update-baseline examples/lbnl_fdd/benchmark-baseline.json
# thereafter, gate (CI fails on a regression beyond tolerance):
python examples/lbnl_fdd/benchmark.py --gate examples/lbnl_fdd/benchmark-baseline.json --tol 0.05

camber.eval.check_against_baseline(current, baseline, *, tol, metrics) is the reusable gate: a higher-is-better metric (TPR, accuracy, correct-diagnosis) regresses when it falls past tol; a lower-is-better one (FPR, error) regresses when it rises past tol; a baseline metric missing from the current run fails too (a detector was removed/renamed). It returns a BaselineCheck (passed, regressions, improvements, unchanged, missing).

.github/workflows/benchmark.yml runs this weekly, on demand, and on PRs that touch the rules or the benchmark — fetching the CC-BY datasets (cached), gating against the committed baseline (or seeding one if absent), and uploading the metrics artifact.

The unified dossier — camber validate

camber validate (module camber.dossier) pulls all five tracks into one artifact — text, a self-contained HTML page, or JSON — so the whole credibility story is legible in one place:

camber validate                       # print the text summary
camber validate --html dossier.html   # write the self-contained HTML dossier
camber validate --json dossier.json   # machine-readable, for release attachment
camber validate --full                # add per-detector / per-family breakdown metrics

It live-recomputes the two pure tracks (synthetic faultlab + generated fleetlab) on every run — no download, deterministic — and cites the three real-data tracks (LBNL FDD, BDG2 M&V acceptance, BDG2 M&V savings) from committed reference figures with provenance and a reproduce command, because they need large datasets. The distinction is shown explicitly (a LIVE vs CITED tag on each track), rates carry their 95% Wilson intervals, and each track states its coverage and honest boundary. The dossier embeds no timestamp — it is anchored on the package version, so two builds are byte-identical (a diff-able release artifact).

The cited figures can't silently rot: tests/test_dossier.py cross-checks the BDG2 numbers exactly against the committed examples/bdg2/benchmark-baseline.json and examples/bdg2/savings-benchmark-baseline.json, and the LBNL numbers against the pooled OA-fraction row in this document — a drift fails CI.

Every tagged release attaches the dossier (dossier.html + dossier.json) as a GitHub Release asset, generated from the packaged version — so each release ships its own version-anchored credibility artifact (site-neutrality-gated alongside the release notes).