AHU / air-side drift detection
The chiller (CHILLER-DRIFT.md) and pump (PUMP-DRIFT.md) families
watch the refrigerant and hydronic sides. The AHU family asks the same "is this slowly getting worse
than it used to be, at matched load?" question of the air side — supply fans, coils, filters, and
duct-static control — reusing the exact same load-normalized frozen-baseline engine
(camber.chillerbaseline, camber.chillerdrift), with an air-side duty normalizer (airflow) in
place of thermal tons.
flowchart TD
base["load-normalized baseline (camber.chillerbaseline, duty = airflow)"] --> det
subgraph det["per-detector drift + CUSUM (camber.chillerdrift)"]
d1[FanEfficiencyDrift]
d2[FilterLoadingDrift]
d3[DuctStaticControlDrift]
d4[CoilValveDrift]
d5[EconomizerDamperDrift]
end
det --> ahu["diagnose_ahu_drift (per-AHU locus, fan-power disambig)"]
ahu --> report["site report / export"]
sim["camber.ahusim (fan laws)"] -. validates .-> ahu
Airflow-normalized baselines feed five per-detector drifts; co-movement rolls up into one per-AHU locus, with ahusim as the physics check.

Synthetic data: ahusim with filter loading, drawn by drift_evidence for filter_loading_drift. At matched airflow the filter's pressure drop has risen well above the frozen baseline's band.
Like the other families, each detector is a period rule (Registry.run_periods), freezes a
load-normalized baseline into a BaselineStore on first use, reports a period statistic and a
sustained-shift CUSUM alarm, labels its thresholds screening-grade / provisional-untuned, and
declines loudly (never reads healthy) when an instrumented point is missing. They complement the
existing static air-side rules (economizer_lockout, satreset, staticreset, airflow) the way
the chiller drift rules complement the static approach check.
The detector family
| Detector | Signal | Normalizer | Sided | Catches |
|---|---|---|---|---|
FanEfficiencyDrift |
supply-fan power | airflow (cfm) | up | wire-to-air efficiency loss — a slipping/worn belt, bearing drag, a degrading motor/VFD, or the fan pushed off its curve; a power excess at matched airflow |
FilterLoadingDrift |
filter differential pressure | airflow (cfm) | up | filter loading (dirty filter) — a DP rise at matched airflow; a fall is a filter change |
DuctStaticControlDrift |
duct static pressure | airflow (cfm) | both | fall = fan cannot hold setpoint (degradation/leakage) vs rise = over-pressurization (sensor-low/stuck damper) — with the static-reset schedule subtracted out |
CoilValveDrift |
cool/heat valve position | delivered air-ΔT (MAT↔SAT) | up | coil fouling / waterside starvation / air bypass / valve-authority loss — valve creep before SAT control fails (econ-gated; waterside-reset caveated) |
EconomizerDamperDrift |
outdoor-air fraction (temp-inferred) | OA-damper command (%) | both | up = damper leaking / stuck-open (excess OA) vs down = damper stuck/slipping closed (lost free cooling / under-ventilation) — degenerate-mixing gated, MAT-stratification caveated |
CoilLeakDrift (opt-in, 0.100) |
valve-shut air rise across the coil (coil leaving or supply air − mixed air) | mixed-air temperature (°F) | down (cooling) / up (heating) | a coil valve passing water while commanded shut — a leak, or a valve stuck partly open; a shifted supply/mixed-air sensor reads the same (caveated). Only when a family entry names coil_leak; judged inside the baseline's mixed-air range only (CLI) |
Fan efficiency is the air-side energy signal. A healthy fan draws a repeatable power at a given
airflow; more power at matched airflow is efficiency loss. It is one-sided up and reuses the
generic Role.POWER on the AHU equip-frame (the equip identifies the fan) with Role.AIRFLOW as the
normalizer — the air-side twin of PumpPowerDrift. Its confound is stated: fan power also rises
when the duct-static setpoint is raised (the fan works harder to hold a higher static), so when a
duct-static point is mapped the rule reports the concurrent static shift and caveats a power excess
that co-moves with rising static.
The economizer detector watches OA delivery, not OA logic. A healthy OA damper delivers a
repeatable outdoor-air fraction for a given command; EconomizerDamperDrift freezes an OAF ~
f(command) baseline — where OAF = 100·(RAT−MAT)/(RAT−OAT) (camber.oafraction) — and scores the
current period's OA-fraction residual at matched command, so mechanical drift (linkage slipping,
seals leaking, the blade sticking, minimum-position creep) shows up as delivery moving while the
command stays put. It is two-sided: more OA than baseline = a leaking / stuck-open damper (excess
outdoor air), less OA = a stuck or slipping-closed damper (lost free cooling, possible
under-ventilation). It is not a sequence check — an economizer commanded wrong for the conditions is
the job of economizer_lockout_rule and freecoolingmissed_rule. Two confounds are handled: the
mixed-air sensor stratifies badly and sits in the numerator, so a standing caveat (Sellers, Relative
Accuracy) flags that and the magnitude floor is set high above it; and where outdoor and return air
are too close (|RAT−OAT| small) the ratio is ill-conditioned, so those rows are excluded before the
fit. Reuses OAT / RETURN_AIR_TEMP / MIXED_AIR_TEMP / OA_DAMPER; no new role. diagnose_ahu_drift
consumes it as the fifth outdoor-air locus (see below).
One per-AHU verdict
The five detectors fail independently (a slipping belt, a dirty filter, a lost static setpoint, a
fouled coil, and a drifting OA damper are different faults) but corroborate when a problem is
AHU-wide. camber.ahudrift.diagnose_ahu_drift(findings) reads them and returns one localized
AhuDriftDiagnosis — naming each cause, flagging corroboration when two or more agree, and running
the fan-power disambiguation that no single signal can do (the air-side twin of pumpdrift's
flow-vs-head check):
- fan-power excess with a loading filter or a rising duct static → the air path (fix the filter / check the ductwork first; the fan power is corroborating, not a separate fan fault);
- fan-power excess with the duct static falling below setpoint → fan degradation;
- fan-power excess with a clean filter and steady static → the fan itself;
- fan-power excess with no filter or static point → called ambiguous rather than asserted.
It splits the AHU into fan (mechanical) / air-path (filter + static) / coil / outdoor-air (economizer
OA mixing) sides, reports a locus (steady · fan · air-path · coil · outdoor-air · ahu-wide) with an
ahu_wide flag, and names a cooling and a heating coil separately. The economizer is an independent
side (like a coil): it corroborates and can make the verdict AHU-wide, but it is deliberately
outside the fan-power disambiguation, because its signal is outdoor-air fraction, not fan power.
Screening-grade; pure over Findings. (The outdoor-air locus is exercised end-to-end by ahusim's
confusion matrix via an OA/RA mixing regime — see Calibration.)
Surfacing the verdict
The per-AHU verdicts flow downstream like the chiller and pump ones:
camber.integrate.export.ahu_diagnoses_to_frame / export_ahu_diagnoses write one row per AHU (locus
· severity · ahu_wide · corroborated · causes · fingerprint) to CSV/JSON/Parquet, and
camber.report.ahu_diagnosis_table renders a worst-first HTML table. build_site_report(...,
ahu_diagnoses=[...]) splices that table into the owner-facing site report, alongside the chiller and
pump verdict tables.
Running the family
From a config, no Python needed — add a drift section naming this family ("family": "ahu") and run
camber drift freeze once to establish the references, then camber drift run to score. camber
run folds the verdicts into the ordinary audit report. Only freeze (and the attributed
accept_new_normal) ever writes a baseline; scoring is read-only. See
CLI.md.
camber drift freeze config.json # establish the references (refuses to overwrite)
camber drift run config.json # score current vs baseline, worst-first
camber drift accept config.json --equip <EQ> --by <NAME> --reason "<what changed>"
Calibration
Thresholds are constructor arguments (screening-grade); the CUSUM parameters are provisional-untuned.
As with the other families, camber.driftvalidation tunes them once labelled AHU-fault periods exist,
and the physics generator camber.ahusim (system curve ΔP ∝ Q² + fan laws) characterizes the family
end-to-end without a dataset — on clear faults the AHU diagnosis localizes to the right locus at
~100% with no false alarms on healthy AHUs or a static-reset schedule, and it proves the fan-power
disambiguation (filter_loading → air-path vs fan_belt_slip → fan). All five loci are exercised,
including outdoor-air: the generator models a genuine OA/RA mixing box (MAT a real mix of a
swept OA-damper command) with two economizer faults — a leaking / stuck-open damper (over-delivery)
and a stuck / slipping-closed one (under-delivery). To keep the coil signal invariant under the mix,
SUPPLY_AIR_TEMP is derived as MAT − dt, so the cooling-coil air-ΔT stays dt by construction
while MAT floats — an economizer fault localizes to outdoor-air alone and leaves the other four
families untouched.
from camber.ahusim import make_cases, locus_confusion
lc = locus_confusion(make_cases(), min_severity=3)
print(lc.accuracy, lc.as_dict()["matrix"])