VAV / zone-terminal drift detection
The chiller (CHILLER-DRIFT.md), pump (PUMP-DRIFT.md), and AHU
(AHU-DRIFT.md) families watch the plant and the air handler. The VAV family asks the
same "is this slowly getting worse than it used to be, at matched load?" question of the zone
terminal — the VAV box's damper, airflow tracking, and reheat coil — reusing the exact same
load-normalized frozen-baseline engine (camber.chillerbaseline, camber.chillerdrift), with the
box's own commanded airflow as the load normalizer.
flowchart TD
base["load-normalized baseline (camber.chillerbaseline, load = commanded airflow)"] --> det
subgraph det["per-detector drift + CUSUM (camber.chillerdrift)"]
d1["VavAirflowDrift (damper creep)"]
d2["VavReheatValveDrift (reheat valve creep)"]
end
det --> box["diagnose_vav_drift (per-box locus, upstream-vs-box)"]
box --> report["site report / export"]
sim["camber.vavsim (LocusConfusion)"] -. validates .-> box
Command-normalized baselines feed the damper- and reheat-valve creep detectors; co-movement rolls up per-box, with vavsim as the physics check.

Synthetic data: vavsim with damper authority loss, drawn by drift_evidence for vav_airflow_drift. The box now needs a wider damper for the same commanded airflow.
Like the other families, each detector is a period rule (Registry.run_periods), freezes a
load-normalized baseline into a BaselineStore on first use, reports a period statistic and a
sustained-shift CUSUM alarm, labels its thresholds screening-grade / provisional-untuned, and
declines loudly (never reads healthy) when an instrumented point is missing. They are the
leading indicators to the existing instantaneous zone rules (airflow_tracking, reheat_penalty,
reheat_minimization_g36, overcooling_min_flow, unmet_setpoint_hours) the way the chiller drift
rules lead the static approach check.
The detector family
| Detector | Signal | Normalizer | Sided | Catches |
|---|---|---|---|---|
VavAirflowDrift |
damper position | commanded airflow (cfm) | up | flow-authority loss — a slipping/worn actuator, a stuck linkage, or rising upstream duct-static starvation: the damper creeps open to hold the same commanded flow, weeks before airflow_tracking sees an undershoot |
VavReheatValveDrift |
reheat valve position | reheat duty ≈ airflow × ΔT (cfm·°F) | up | reheat-coil heat-transfer loss — waterside fouling/scale, low HW flow/ΔT, air bypass, or valve-authority loss: the reheat valve creeps open to deliver the same reheat, weeks before the box misses setpoint and reheat_penalty / reheat_minimization_g36 see it |
Airflow tracking is the leading indicator to airflow_tracking. A healthy box drives its damper
to make measured airflow track the commanded airflow setpoint. As the actuator/linkage wears or the
box is starved of upstream static, it spends its reserve damper authority — the damper creeps
further open while flow still tracks — so the instantaneous airflow_tracking undershoot check sees
nothing until the damper saturates near 100%. VavAirflowDrift freezes a damper ~ f(commanded
airflow) baseline and scores the current period's damper residual at matched command: a creep is
authority loss. It is one-sided up (needing less damper is an authority gain, not a fault), and
it is the terminal-box analog of the coil-valve-creep → SAT-control relationship.
The airflow-setpoint confound is neutralized by construction. A VAV setpoint moves constantly
(Guideline-36 dual-max, zone demand, reset) — but the setpoint is the load axis here, so normal
setpoint motion just walks the box along the same frozen curve and scores ~0 residual. (Unlike
duct_static_drift, where the confounder is in the metric's own unit and a residual subtraction is
right, here the confounder is the x-axis and the matched-command geometry does the work.)
Upstream starvation is surfaced, not blamed. A damper can creep because its own actuator is
failing or because upstream duct static is low (an AHU/fan problem). When a building-level
DUCT_STATIC point is mapped (via the runner's shared channel), the rule reports the concurrent
static shift and caveats a creep that co-moves with a static fall (vav_upstream_starvation_suspected),
so it never silently blames the box for a plant problem. Reuses only existing roles
(DAMPER / AIRFLOW_SP; load_role=AIRFLOW is a constructor option for boxes without a mapped
setpoint). Freezes under model kind vav_damper.
Reheat-valve creep is the leading indicator to reheat_penalty / reheat_minimization_g36. A
box's hot-water reheat coil losing heat-transfer capacity (waterside fouling/scale, low HW flow or
ΔT, air bypass, valve-authority loss) opens its valve further to deliver the same reheat — weeks
before it runs out of valve and misses setpoint. VavReheatValveDrift freezes a valve ~ f(reheat
duty) baseline and scores the current period's valve residual at matched duty, one-sided up (a
valve fall is a capacity gain, not a fault). The load is the reheat duty ≈ airflow × ΔT, not ΔT
alone: unlike an AHU coil at fixed design airflow, a VAV box's airflow varies (Q ∝ airflow × ΔT),
and — contrary to the tempting "G36 pins reheat at min flow" simplification — flow rises toward
heating-max in the high heating loop (exactly the regime reheat_minimization_g36 flags), so duty is
correct across both regimes while ΔT-alone is confounded. The box's entering primary air is mapped
to MIXED_AIR_TEMP (the coil-valve heating convention: warm = SUPPLY_AIR_TEMP discharge, cool =
MIXED_AIR_TEMP entering, ΔT = warm − cool) since the box's own discharge already owns
SUPPLY_AIR_TEMP; no new role. A colder HW-supply reset is caveated (it needs more valve for the
same reheat), not subtracted. load_basis="deltat" is a constructor option for boxes without a
mapped flow. Freezes under model kind vav_reheat_valve.
One per-box verdict
The two detectors fail independently (a failing damper actuator and a fouling reheat coil are
different faults) but corroborate when a box is broadly degrading.
camber.vavdrift.diagnose_vav_drift(findings) reads them and returns one localized
VavDriftDiagnosis — naming each cause, flagging corroboration when both agree, and running the
upstream-vs-box disambiguation that no single signal can settle (the terminal-box twin of
diagnose_ahu_drift's fan-power disambiguation):
- damper creep with
vav_upstream_starvation_suspected(the creep co-moves with an upstream duct-static fall) → the drift is a plant symptom — the AHU can't hold static, so the box damper creeps open; locusupstream, "fix the plant, not the box"; - damper creep without it → the box's own flow-authority loss; locus
airflow; - reheat-valve creep → reheat coil fouling / HW starvation / valve-authority loss; locus
reheat(a co-moving HW-supply fall is caveated as a possible waterside-reset effect).
It splits the box into an airflow (damper authority) and a reheat (coil) subsystem, reports a
locus (steady · airflow · reheat · upstream · box-wide) with a box_wide flag. An upstream
verdict is a plant symptom and is deliberately excluded from box_wide — an AHU static problem
must not read as a broadly-failing box, so upstream + reheat resolves to locus reheat (with an
upstream caveat), and only airflow + reheat (two real box faults) is box-wide. Screening-grade;
pure over Findings.
Surfacing the verdict. The per-box verdicts flow downstream like the chiller, condenser,
evaporator, pump, and AHU ones: camber.integrate.export.vav_diagnoses_to_frame /
export_vav_diagnoses write one row per box (locus · severity · box_wide · corroborated · causes ·
caveat count · fingerprint) to CSV/JSON/Parquet, and camber.report.vav_diagnosis_table renders a
worst-first HTML table. build_site_report(..., vav_diagnoses=[...]) splices that table into the
owner-facing site report, alongside the plant, pump, and AHU verdict tables.
Running the family
From a config, no Python needed — add a drift section naming this family ("family": "vav") and run
camber drift freeze once to establish the references, then camber drift run to score. camber
run folds the verdicts into the ordinary audit report. Only freeze (and the attributed
accept_new_normal) ever writes a baseline; scoring is read-only. See
CLI.md.
camber drift freeze config.json # establish the references (refuses to overwrite)
camber drift run config.json # score current vs baseline, worst-first
camber drift accept config.json --equip <EQ> --by <NAME> --reason "<what changed>"
Calibration
Thresholds are constructor arguments (screening-grade); the CUSUM parameters are provisional-untuned.
As with the other families, camber.driftvalidation tunes them once labelled VAV-fault periods
exist, and the physics generator camber.vavsim characterizes the family end-to-end without a
dataset. Because the diagnosis returns a locus, it scores a LocusConfusion over the five loci
(steady · airflow · reheat · upstream · box-wide) — like ahusim/pumpsim, not the CauseConfusion
of the condenser/evaporator sims.
The generator models a single two-regime diurnal box: occupied-daytime cooling (a swept command
+ modulating damper + closed reheat) feeds VavAirflowDrift, and night/morning heating (minimum
airflow + a modulating reheat valve) feeds VavReheatValveDrift — each detector's gating carves out
its own regime. The upstream-vs-box disambiguation is directly measured: damper_authority_loss →
airflow and upstream_starvation → upstream inject the same damper creep, and only the latter also
drops the upstream DUCT_STATIC (tripping vav_upstream_starvation_suspected); box_wide → box-wide.
On clear faults the diagnosis localizes at ~100% with no false alarms on healthy boxes.
One honest asymmetry: the airflow detector cleanly re-routes an upstream cause to a distinct
locus, but the reheat detector only caveats a hot-water-reset creep (its HW confound is a caveat,
not a locus demotion). So the generator carries a mild hw_reset as a steady negative, and the
fire-with-caveat behavior of a strong HW reset is covered by a dedicated test.
from camber.vavsim import make_cases, locus_confusion
lc = locus_confusion(make_cases(), min_severity=3)
print(lc.accuracy, lc.as_dict()["matrix"])