CAMBER's Role vocabulary is the hub; camber.interop maps it to and from the building-ontology models other tools share, so an already-tagged building needs no hand-written mapping and CAMBER's model can be exported for downstream use.

flowchart LR
  brick["Brick model (ttl)"]
  hay["Haystack tags"]
  s223["ASHRAE 223P (ttl)"]
  role["Role vocabulary"]
  brick -- "mapping_from_brick" --> role
  hay -- "roles_from_haystack" --> role
  s223 -- "site_from_223" --> role
  role -- "to_brick" --> brick
  role -- "haystack_tags" --> hay
  role -- "site_to_223" --> s223

The Role vocabulary is the hub: camber.interop imports from and exports to each ontology.

Brick

  • Import — mapping_from_brick / roles_from_brick derive Role mappings from a Brick model (point classes + hasPoint/hasPart relationships). See camber/interop/brick.py. These roles can come from a Brick model: air-side temperatures, pressures, flows, humidity, CO₂ and setpoints; the hot-/chilled-/condenser-water plant (supply/return temperatures, CHW supply setpoint, loop DP and DP setpoint, water flow); and, from the owning equipment's class, coil valves, the outdoor-air damper, supply-fan / hot- and chilled-water-pump / tower-fan speed, supply-fan and pump status, boiler run status, equipment power, and zone heating/cooling setpoints. The others (refrigerant-side temperatures and pressures, DX stages and statuses, mode flags, reset-request counts, the terminal damper, thermal energy rate, pump head, among others) have no Brick class CAMBER maps yet.
  • Import review — brick_mapping_report(ttl) — the same import, per point: mapped (a standard class), alias (a non-standard class accepted with a caveat), ambiguous (a role is plausible but the model does not pin it down — not mapped, with the reason) or unmapped (no CAMBER role). report.summary() prints the review; report.roles is what roles_from_brick returns. Rules it applies, all generic (no building is special-cased):
  • Obvious non-standard classes are accepted with a caveat (ALIAS_CLASS_TO_ROLE): Outdoor_Air_Flow_Rate → oa_airflow, an Outdoor_Air_Damper equipment class used as a point type → oa_damper, Supply_Air_Fan_Speed → supply_fan_speed, Hot_/Chilled_Water_Supply_Flow_Rate → hw_flow / chw_flow, and the Outdoor_ spelling of any Outside_ class. Classes with no CAMBER meaning (e.g. Economizer_Setpoint) are listed, never guessed.
  • A flow class on a point named like a speed/percent is never mapped — a Supply_Air_Flow_Sensor called …_fan_spd is ambiguous, so a 0–100 % series never reaches a cfm rule. (mapping_confidence catches the same thing from the data; see MAPPING-ASSIST.md.)
  • An enable is never a running status. Run_Status on a boiler → boiler_status; a boiler's On_Off_Status (in published models often the plant enable, on all season) and any Enable_Status / Enable_Command are ambiguous. Mapping an all-season enable as firing status reads every enabled-but-idle hour as firing — e.g. a summer-lockout fault on every day.
  • Component power is not equipment power. Electrical_Power_Sensor → power on a pump, chiller, boiler, tower or packaged unit; on a fan inside an air handler it is ambiguous.
  • Leaving/entering water is plant supply/return only on a boiler, chiller or loop (a coil's leaving water is its return). Hot_/Chilled_Water_Temperature_Sensor with no supply/return, a pump speed whose loop the pump class does not state, and Occupant_Count (a head count, not binary occupancy) are ambiguous.
  • Commands are a fallback. Valve_Command / Damper_Position_Command / Speed_Command map (through the same owner context) only when the owner has no position/speed feedback.

On the published LBNL boiler-plant model this maps 17 of 22 points (previously 1: the plant classes were missing), with both boiler on/off statuses reported ambiguous and gas meters / heating demand listed as unmapped. - Export — to_brick(equip_id, equip_class, roles) emits Brick Turtle for 40 of 84 roles (every direct class the importer knows, plus the coil-valve / OA-damper / supply-fan part context). Export and import are exact inverses: a test enumerates every role the exporter can emit and re-imports it on both parsers (the CO₂, outdoor-air flow, outdoor CO₂/RH and airflow setpoint classes the exporter emitted were previously dropped on re-import, so DCV roles could never come from a Brick model). - Whole-site round-trip — site_to_ttl / site_from_ttl round-trip a Site→Equip→Point model (with relationships); minimal parser by default, rdflib used when the [brick] extra is present. Since 0.108 each equipment has its own part nodes (bldg:AHU_1.Cooling_Coil, bldg:AHU_2.Cooling_Coil, not one shared bldg:Cooling_Coil), so with several air handlers each one gets back only its own valves, dampers and fan points. The importer reads a part's name as what follows the last dot, so AHU_1.Supply_Air_Fan is still a supply fan. - Names are encoded, labels are exact (0.108) — real point and equipment names (SA Temp, AHU-1/SAT, SAT., AHU_1:supply_air_temp, non-ASCII) are written as valid Turtle local names: letters, digits, _ and - stay as they are, and every other character is percent-encoded (bldg:AHU%201, bldg:AHU-1%2FSAT). Each node also carries its exact name as rdfs:label. Both readers (rdflib and the minimal one) decode the local name back, so names round-trip exactly and the default Equip.from_roles names of two air handlers no longer collide. A model written by another tool is read as before; a percent-encoded name in it is decoded the same way. The minimal 223P export (site_to_223) encodes equipment ids the same way.

from camber.interop.export import to_brick
from camber.interop.brick import roles_from_brick
from camber.model.roles import Role

ttl = to_brick(
    "AHU 1", "AHU", [Role.SUPPLY_AIR_TEMP], point_names={Role.SUPPLY_AIR_TEMP: "SA Temp"}
)
assert "bldg:SA%20Temp" in ttl and 'rdfs:label "SA Temp"' in ttl
assert roles_from_brick(ttl, backend="minimal") == {"SA Temp": Role.SUPPLY_AIR_TEMP}
- Served-by topology — topology_from_brick(ttl) builds a Topology (see TOPOLOGY.md) from brick:feeds / isFedBy; site_from_ttl auto-populates Site.topology from those relations.

Project Haystack

  • Export — haystack_tags(role) / equip_haystack_tags(roles) emit a role's marker-tag set (from HAYSTACK_HINT). camber/interop/export.py.
  • Import (0.6) — role_from_tags(tags) / roles_from_haystack(points) / mapping_from_haystack recover roles from a point's marker tags, closing the round-trip to Brick-level parity. A role matches when its hint tag-set is a subset of the point's tags; the most specific hint wins ties (so …temp sp beats …temp sensor). Accepts (name, tags) pairs or Haystack tag dicts. Every role round-trips export→import (a test checks each one). A few roles also carry excluding tags: the terminal damper role (hint damper cmd) does not match a point that names an air stream (return / exhaust / relief / mixed), since those are air-handler dampers with no CAMBER role — previously every return and exhaust damper imported as a VAV-box damper. camber/interop/haystack_semantic.py.
  • Served-by topology — topology_from_haystack(entities) builds a Topology from ahuRef / equipRef reference tags (see TOPOLOGY.md).
  • JSON encodings (0.108) — both functions take the rows of a Haystack read grid in any of the standard JSON encodings. A marker is true, "M", "✓", Haystack JSON v3's "m:" or Hayson's {"_kind": "marker"}. A ref is "@id", v3's "r:<id> <dis>" or Hayson's {"_kind": "ref", "val": "<id>"}, and it resolves to the bare id, for a point's id and for ahuRef / equipRef. Before 0.108 the v3 and Hayson forms resolved nothing. The test fixtures tests/golden/haystack/read_v3.json and read_hayson.json are one small site in each encoding.
from camber.interop.haystack_semantic import roles_from_haystack
from camber.model.roles import Role

v3 = {"id": "r:p1 OAT", "point": "m:", "outside": "m:", "air": "m:", "temp": "m:", "sensor": "m:"}
hayson = {
    "id": {"_kind": "ref", "val": "p1"},
    **{t: {"_kind": "marker"} for t in ("point", "outside", "air", "temp", "sensor")},
}
assert roles_from_haystack([v3]) == roles_from_haystack([hayson]) == {"p1": Role.OAT}

ASHRAE 223P (minimal profile)

ASHRAE Standard 223P is an RDF/SHACL semantic model for building systems — equipment, connections, media, and the physical properties they observe. The full standard is large, SHACL-validated, and still maturing, so camber.interop.semantic223 exports/round-trips a deliberately minimal profile: equipment, their observable properties, and each property's QUDT quantity-kind + medium derived from the role.

from camber.interop import site_to_223, site_from_223

ttl = site_to_223(site, profile="minimal", include_relations=True)
site2 = site_from_223(ttl)  # round-trips equip_class + the points' roles

Mapping coverage was broadened in 0.6 from 21 to 44 of the then 54 roles — the full plant/hydronic side (CHW/HW/CW temps, loop pressures, pump/tower speeds), power/thermal energy, ambient/humidity, and the refrigerant-side approach temps; the vocabulary has since grown, and today 71 of 84 roles map. The remaining 13 roles are binary/enumerated status & command signals and counts (*_status, *_stage, reversing_valve_cmd, econ_cmd, warm-up/cool-down, the G36 reset-request counts) that carry no QUDT quantity-kind; they are listed in _NO_223_QUANTITY and intentionally omitted from the quantity map (223P models them as enumerated states). A test asserts the mapped + unmapped sets partition every role, so a newly-added role can't be silently forgotten.

Mapping (ROLE_TO_223, role_223_quantity): e.g. SUPPLY_AIR_TEMP → (Temperature, Air), OA_AIRFLOW → (VolumeFlowRate, Air), CHW_FLOW → (VolumeFlowRate, Water), valves/dampers → PositionRatio. The emitted Turtle types each equipment as s223:Equipment (with the CAMBER equip_class as rdfs:label) and each point as s223:Property with s223:hasQuantityKind and s223:ofMedium, linked by s223:hasProperty.

Option flags — site_to_223

flag default effect
profile "minimal" minimal emits only role-mapped properties; full also emits unmapped roles as a generic dimensionless property
include_relations True emit the equip→property s223:hasProperty edges

Scope & honesty

This is a profile, not a conformance claim. It captures the equipment/property/quantity layer of 223P that maps cleanly from CAMBER's model; it does not assert full Standard-223 conformance (which requires validation against the published SHACL shapes and richer connection/medium modeling). Serialization is plain Turtle and the reader is a string parser, so no new dependency is required.

Served-by topology from 223P is deferred. 223P models flow as a multi-hop connection graph (Equipment → ConnectionPoint → Connection → ConnectionPoint → Equipment, medium-typed) rather than a single parent reference, and CAMBER emits none of it, so extracting a served-by Topology from 223P is left to a later release — Brick feeds (above) covers the authoritative-semantic layer today.