A hands-on course in building re-tuning, run on open data with CAMBER. It follows the free Building Re-tuning training from the Pacific Northwest National Laboratory (PNNL): read a chapter or a guide there, then open a real or simulated building in camber lab and find the problems it teaches you to look for.

Status (0.97, provisional). All 20 exercises in the map below are written: five on the air side, five on terminal units and ventilation, six on the central plant, and four on data quality, M&V and the capstone. Start with the worked example, Economizer: a stuck outdoor-air damper and missed free cooling.

How it works

  • Read PNNL, then practise here. Each exercise names the PNNL chapter or guide to read first, in its Learn more section. The workbook links to PNNL's documents and never copies them; the links come from CAMBER's reference registry.
  • Open data only. Core exercises use open-licence datasets from the catalog. A research-only dataset appears only as a marked optional extra. Where no open dataset shows a fault, an exercise uses a synthetic dataset that CAMBER generates on your computer, labelled synthetic wherever it appears (0.103: plant-lockout).
  • Two ways in. Every exercise gives the steps both in the lab (a local web page: camber lab, then Fetch & ingest, trends, report) and on the command line.
  • Tuned configs. Where the dataset's default config doesn't fit an exercise, the exercise ships its own: camber datasets config <dataset> --exercise <exercise-id> --store lab_store --out cfg.json.
  • Answers are checked. The instructor's key is on a separate instructor page. Every answer on it is pinned by CAMBER's test suite, on a small synthetic stand-in for each dataset and, optionally, on the real data, so the key cannot silently drift from what CAMBER shows.

Getting started. Install CAMBER, then:

camber lab

Open the URL camber lab prints (http://127.0.0.1:8765/lab?token=...: the token is a new secret each run), tick a dataset and press Fetch & ingest. A dataset used by an exercise has an exercise link in its row. From a source checkout, the lab serves the page itself, so it opens offline; otherwise the link goes to this site. New to the lab? Using the lab walks through a first session step by step, and its classroom section covers pre-fetching the datasets for an offline room.

Curriculum map

The tables map each PNNL chapter or guide to its exercises and datasets. Exercise ids are stable: they name the page (<id>.md) and the tuned config (--exercise <id>).

Air side

PNNL reading Exercise Datasets
Ch. 5, AHU Discharge-Air Temperature Control air-sat-reset: supply-air temperature reset lbnl-sdahu, lbnl-ddahu, irish-ahu
Ch. 5, AHU Static Pressure Control air-static-pressure: a fixed static setpoint and the damper census lbnl-sdahu, ornl-frp-vav
Ch. 5, AHU Heating and Cooling Control air-heat-cool: a leaking valve, and coils that fight lbnl-sdahu, lbnl-ddahu, irish-ahu
Ch. 6, Air-Side Economizer Operation air-economizer: a stuck outdoor-air damper and missed free cooling lbnl-sdahu, irish-ahu
Ch. 5, Occupancy Scheduling air-scheduling: 24/7 operation, night setback and after-hours fan energy ornl-frp-ops

Terminal units and ventilation

PNNL reading Exercise Datasets
Ch. 7, Zone Heating and Cooling Control zone-reheat-overcooling: reheat penalty and overcooling lbnl-fpu
Ch. 7 zone-bad-box: one bad box in a fleet ornl-frp-vav
Ch. 7, Zone Heating and Cooling Control zone-reheat-saturated: a zone below setpoint with its reheat maxed out lbnl-fpu, ornl-frp-vav
Ch. 5, AHU Minimum Outdoor-Air Operation zone-dcv: is outdoor air following occupancy? finnish-dcv, b4b-windesheim, sdu-ou44
Ch. 5, AHU Minimum Outdoor-Air Operation zone-min-oa: minimum outdoor air and 62.1 system ventilation lbnl-b59

Central plant

PNNL reading Exercise Datasets
Ch. 8, Central Utility Plant Cooling Control plant-chiller-efficiency: chiller efficiency, a calibrated ceiling and fouling lbnl-chiller
Ch. 8 plant-cooling-tower: approach, fan effort and a leaking tower bypass lbnl-chiller
Ch. 8, Central Utility Plant Cooling Control plant-chw-reset-pumping: chilled-water reset, low delta-T and pumping lbnl-chiller
Ch. 8, Central Utility Plant Heating Control plant-boiler: hot-water reset, summer lockout, pumping and a fouling gap lbnl-boiler
Ch. 8, Central Utility Plant Heating Control plant-lockout: a boiler and a pump left on in warm weather, and choosing the lockout synthetic-hw-plant-lockout (synthetic)
Ch. 8 plant-sensor-vs-equipment: sensor faults vs equipment faults lbnl-chiller

Data quality, energy charting, M&V and the capstone

PNNL reading Exercise Datasets
Ch. 3, Ch. 4, Trending Requirements data-trend-quality: are the trends good enough? lbnl-b59, irish-ahu, nuig-ahu101
Ch. 4, Occupancy Scheduling data-energy-charting: load profiles and weather dependence bdg2, valladolid-uva
Ch. 4, Ch. 10 mv-baselines: change-point baselines and M&V valladolid-uva, cofactor-drammen, bdg2 (synthetic bills)
Economizer, Ch. 9, Ch. 10 capstone: the RCx report, a walk-down list, a re-tuning plan, verification lbnl-sdahu, ornl-frp-ops

Going further: tune the thresholds yourself

Several exercises tune a rule to its dataset's unit, such as a design minimum outside air or a fixed high limit. When you apply the same rules to your own building, re-tune them the same way. camber rules params RULE shows each threshold's default, where the default comes from, and how to calibrate it. Tuning thresholds with your own data walks through calibrating on a known-good period, keeping the scoring data separate from the calibration data, and recording the calibration in a YAML config comment. Its worked examples use the catalog datasets from these exercises.

For instructors

The instructor page holds the answer keys, discussion points and common mistakes. Keep it away from learners until they have tried the exercise.