Skip to content

Tuning thresholds with your own data

Every rule threshold in CAMBER is a starting point. Most defaults are engineering judgment, not measurements of your building, and THRESHOLDS.md says which ones. This page is about re-tuning them as you collect data, without fooling yourself.

Status (0.98, provisional). camber rules params, the YAML config format and the basis provenance map are new in 0.98 and may still change before 1.0.

The short version

  1. Find the knob. camber rules params RULE lists the rule's parameters with their defaults, units, sensible ranges, where each default comes from, and how to calibrate it.
  2. Calibrate on a period you know is good: a commissioning week, the month after a repair, a fault-free run in a labelled dataset. Take a robust statistic (a median, a 95th percentile) of the quantity the parameter bounds.
  3. Score on data you did not calibrate on. A different period, a different unit, or a held-out half. A threshold fitted to the data it is then judged on will look better than it is.
  4. Write down what you did, in the config, beside the value: the data, the period, the statistic and the scoring data. YAML configs keep that as comments; the basis map copies it into every finding of the rule.
  5. Re-check against labelled data when you have it: a confirmed fault, a service ticket, a catalog dataset with fault labels.

1. Find the parameter

camber rules params                     # every rule
camber rules params leaking_valve       # one rule: default, unit, range, basis, how to calibrate
camber rules params leaking_valve --yaml > leak.yaml   # a config snippet, notes as comments
camber rules params --json              # machine-readable, for your own tooling

The same information, for every rule, is in THRESHOLDS.md. Its basis column tells you how much to trust a default:

  • standard: ... is a value the code takes from a cited standard section. Change it only when your sequence of operation says otherwise.
  • public source: ... comes from a published guide (a PNNL Re-tuning chapter, for example). It is a sensible starting point, not a measurement of your building.
  • CAMBER judgment is an engineering choice, usually screening-grade. Re-tune these first.
  • calibrated on ... was fitted to the named data. Check whether your building resembles it.

Some thresholds are still fixed in code, and THRESHOLDS.md lists them under Fixed in code. If you need one of them tuned, please open an issue.

2. Calibrate on a known-good period

A threshold separates normal from faulty, so learn "normal" from data you trust:

  • A commissioning or post-repair period. After a TAB report, a valve replacement or a sensor calibration, the next few weeks are your best known-good data.
  • A fault-free run. Labelled datasets (the lbnl-* simulations, nist-heatpump-fdd) ship runs with no fault injected.
  • The design documents. A sequence of operation, a TAB report or a nameplate is independent of the trends, so it is the cleanest basis of all: a design minimum outside-air fraction, a design loop ΔT, a charging target.

Then measure the quantity the parameter bounds, over the conditions the rule judges (fan on, occupied, running, and so on), and take a robust statistic:

  • A normal level (a fan heat, a design minimum OA fraction, a target subcooling): take the median.
  • A noise band (a tolerance, a "closed" valve position, a deadband): take a high percentile (the 95th) of the fault-free spread, then leave a margin above it.
  • A severity share (warn_pct, fault_pct): look at the metric the finding reports on units you know are healthy, and set the level well above their spread.

The findings help. Most rules report the statistic their threshold is compared with (for example median_delta_f for leaking_valve, simultaneous_hc_pct for simultaneous_heat_cool), so a run on the known-good period at the default settings shows where normal sits.

Drift references

The drift detectors take the same idea one step further: "normal" is a fitted model of the equipment, not a single threshold. Usually that model is the unit's own baseline, frozen once with camber drift freeze. When the known-good data is somewhere else, declare it as the family's reference instead (how):

  • A known-good period of the same unit, {"period": [start, end]}: a post-commissioning season, the weeks after a repair. The current window then starts where that period ends, so the two never overlap.
  • A unit known to be healthy, {"equip": ID}: a labelled dataset's fault-free run, or a sister unit of the same design and sequence. This is the "split by unit" of the next section, so it is sound only when the units are alike.

A declared reference is re-fitted on every run and never stored, and the reference unit declines (is_reference) rather than scoring itself. Record why it is known to be good in the config's _comment, as for any calibrated value. The lbnl-chiller and lbnl-boiler templates score cooling_tower_fan_effort_drift and boiler_efficiency_drift against PLANT__fault_free this way (PLANT-DETECTORS).

A leak is a case where the drift form removes a calibration altogether. leaking_valve needs the unit's fan heat to see a small cooling leak (the circularity below). The opt-in coil_leak_drift detector instead fits the unit's valve-shut rise from mixed to supply air on a known-good period, so the fan heat is part of the baseline and nothing is calibrated on the window it scores (CLI, VALIDATION).

3. Avoid circular calibration

If you calibrate on a period and then score on the same period, the score is not evidence. The threshold was chosen to call that period normal, so of course it does. Keep calibration and scoring apart:

  • Split in time. Calibrate on one period and judge the next. A store source takes a window: "source": {"kind": "store", ..., "start": "2018-01-01", "end": "2018-06-30"}.
  • Split by unit. Calibrate on some units and judge the others. This is sound only when the units are alike (same design, same sequence).
  • Leave one out. With few labelled runs, calibrate on all but one and score the one left out, then repeat for each.
  • Say so when you cannot. Sometimes the only good data is the data you judge. That is acceptable for a first pass, but write it down, and do not quote the result as a detection rate.

4. Record the provenance in the config

JSON has no comments, so JSON templates carry a top-level "_comment". YAML (the optional [yaml] extra: pip install 'camber-toolkit[yaml]') lets the note sit beside the value:

rules:
  - name: outdoor_air_fraction
    params:
      # Calibrated on AHU-3, 2026-03-02..03-29, fan on + occupied (41,000 minutes): median OA
      # fraction 14.2 %. TAB report 2025-11 design minimum: 15 %. Scored on April-June only.
      min_oa_pct: 14.0
    basis:
      min_oa_pct: "calibrated on AHU-3 March 2026 (median fan-on OA fraction); TAB 15 %"

The optional basis map is copied into each finding of that rule as metrics["param_basis"] ({"min_oa_pct": {"value": 14.0, "basis": "..."}}). The provenance then travels into findings.json, the reports and the fault register. A basis for a parameter you did not set records the default. A misspelt name is an error.

JSON and YAML configs that say the same thing give identical results. camber run, camber report, camber explain, camber drift, camber fleet and python -m camber.config all read .yaml / .yml. To start from a catalog template in YAML:

camber datasets config lbnl-sdahu --store lab_store --out sdahu.yaml   # or --format yaml

The template's notes become comments, so you can edit the values with their reasons beside them.

5. Re-check against labelled data

A threshold that looks right on healthy data can still miss faults. When you have labels, score the tuned config and compare it with the defaults:

camber run tuned.yaml --out tuned
camber datasets score lbnl-sdahu --store lab_store --findings tuned/findings.json

datasets score gives the true-positive rate, the false-positive rate and accuracy, each with a 95% interval. On a few labelled runs the intervals are wide, so read a one-run change as noise until more data agree. On your own building, a confirmed fault (a work order, a service report) is a label too: check that the tuned threshold still flags it.

Worked examples on open data

Each example uses a dataset from the catalog. Fetch and ingest it first (camber lab, or camber datasets fetch ID then camber datasets ingest ID --store lab_store).

A design minimum outside air (lbnl-sdahu, outdoor_air_fraction)

The default min_oa_pct is a generic 20%. The lbnl-sdahu unit is not generic. Its sequence (inventory section 1.2) holds the damper at a fixed 10% position, which measures as a 1.6% OA fraction.

  1. Calibrate. Run outdoor_air_fraction on the fault-free run, AHU__fault_free, over occupied, fan-on samples. The median OA fraction of its 119,163 occupied, fan-on minutes is 1.6%, and the dataset template sets min_oa_pct: 1.6 with that note in its _comment (camber datasets config lbnl-sdahu --format yaml shows it as a comment).
  2. Check it independently. The inventory's fixed damper position is a design document, not the trends, so it corroborates the calibrated value without reusing the scored data.
  3. Know what is circular. AHU__fault_free is also one of the negatives when the dataset is scored. Its clean verdict at 1.6% is therefore partly by construction. The evidence is the verdicts on the damper-fault runs, which the calibration never saw. For a cleaner split, set source.start / source.end to calibrate on one half of the year and judge the other half.

A charging target (nist-heatpump-fdd, dx_refrigerant_charge)

The rule compares each unit's liquid subcooling with a target. The dataset does not publish the nameplate targets, so the template uses each unit's fault-free median subcooling: 8.6 °F on the 14 SEER unit and 9.7 °F on the 16 SEER unit.

  1. In-sample (the template). The targets come from the fault-free runs, and those runs are then scored. FDD-DX.md reports 24/24 charge runs caught at 0/4 false alarms. The 0/4 is in-sample: those four runs set the targets.
  2. Held out. When the fault-free runs are split into two halves by file (calibrate on one half, judge the other), the rule catches 23/24 charge runs at 0/8 false alarms. Leaving each test file out of its own baseline gives 86/95 files caught at 7/90 false alarms. These are the numbers to quote. They are honest because no scored file set its own threshold.
  3. What to take away. Calibration on fault-free data worked, since the held-out rates are close. But only the held-out rates show that, and they are what a new building would see.

A known circularity (lbnl-sdahu, leaking_valve)

leaking_valve allows for the supply fan's heat when it judges a heating leak (fan_heat_f, 2 °F by default, the ASHRAE Guideline 36 initial value), but by default credits none to the cooling-leak test. On lbnl-sdahu, the fault-free run's median rise from mixed air to supply air, with both valves closed and the fan on, is about 1 °F, and the published 10 % leak only cancels it. The 0.98 template sets measured_fan_heat_f to 1.0 °F, calibrated on that run, and the fault-free run is again a scored negative: its clean verdict is in-sample. The template comment (and its basis map) and VALIDATION.md state the circularity, and VALIDATION.md gives the half-year split (calibrate on one half, judge the other) that shows the value holds. When you reuse a calibrated value from a template, check its note for the same trap.

Your own building

With no labels, the procedure is the same, only slower:

  1. Pick a known-good month, just after commissioning or a repair.
  2. Run the rules at their defaults on it, and read the finding metrics each threshold is compared with.
  3. Set the parameters from those statistics, with a margin, and write the notes in the YAML.
  4. Judge the following months. When a finding is confirmed or dismissed on site, record it. Those records are your labels for the next round of tuning.

A climate-dependent default: the free-cooling high limit (free_cooling_missed)

free_cooling_missed counts an hour as free-cooling weather when the outdoor air is below high_limit_f. The default, 60 °F, is CAMBER's deliberately conservative screening value. Below it, an economizer should be cooling with outside air in nearly any climate, so an hour of mechanical cooling there is clearly a missed hour. The library function camber.freecooling.free_cooling_opportunity uses the same default (DEFAULT_FREE_COOLING_HIGH_LIMIT_F). Before 0.98 it used 65 °F, so a direct call with no high_limit_f now counts fewer hours. The rule and the reports are unchanged: the RCx report's economizer page passes economizer_high_limit's high_limit_f and prints the value it used.

The right value for a building is the dry-bulb high limit its economizer is designed to run to, and that depends on climate:

  • Read the sequence first. If the unit's economizer sequence states a fixed dry-bulb high limit, use it, or a degree or two below it so that only clearly cool weather counts.
  • Otherwise use the energy code for the site's climate zone. ASHRAE 90.1 (§6.5.1.1.3) tabulates the fixed dry-bulb high limit by climate zone. Dry climates, where outdoor air stays useful up to a higher dry-bulb, get a higher limit. Humid climates get a lower one, because warm humid air adds latent load. The PNNL Air-Side Economizer Operation guide (reference pnnl-guide-economizer, see REFERENCES.md) covers the same check from the re-tuning side.
  • Or read it from the trends. Over a summer of known-good operation, the highest OAT at which the OA damper still opens fully is the high limit the unit actually runs.
  • Keep it at or below the unit's real limit. A high_limit_f above the high limit the economizer is programmed with counts hours when the economizer is correctly locked out as "missed", and the rule then reports a working unit as a fault.

economizer_high_limit has its own high_limit_f (65 °F), which is the other side of the same setpoint: it checks that the damper closes above the limit. On a tuned site, set both from the same sequence value.

The low limit (0.100). Many sequences also lock the economizer out below a low outdoor-air temperature (freeze protection) and hold the OA damper at its minimum. Mechanical cooling in that weather is not missed free cooling, so set free_cooling_missed's low_limit_f to the lockout in the unit's sequence. Hours below it are then left out of the free-cooling weather and reported as low_limit_excluded_hours. The default, None, assumes no lockout. From trends, the lockout is the OAT below which the OA damper command never leaves its minimum over a known-good winter. The lbnl-sdahu template sets its documented 33.8 °F. Without it, that unit's fault-free run reads warn, because nearly all its "missed" hours are lockout hours.

See also

  • THRESHOLDS.md: every parameter, its basis and calibration hint (generated).
  • CLI.md: camber rules params, camber datasets config --format.
  • VALIDATION.md: how CAMBER's own detection rates are measured.
  • The re-tuning workbook: exercises that tune a rule to a dataset's unit.